Technical data
Liquisys M CUM223/253
98
Hauser
Controller
Alarm
Protocol specific data
Function (adjustable):
pulse length/pulse frequency controller
Controller response:
PID
Control gain K
p
:
0.01 to 20.00
Integral action time T
n
:
0.0 to 999.9 min
Derivative action time T
v
:
0.0 to 999.9 min
Period for pulse length controller:
0.5 to 999.9 s
Frequency for pulse frequency controller:
60 to 180 min
-1
Basic load:
0 to 40% of max. set value
Function (selectable):
Latching / momentary contact
Alarm threshold adjustment range:
Turbidity / suspended solids / temperature:
complete measuring range
Alarm delay:
0 to 2000 s
0 to 2000 min
HART
Manufacturer ID
11
h
Device type code
0095
h
Transmitter specific revision
0001
h
HART specification
5.0
DD files
www.products.endress.com/hart
Load HART
250
Device variables
None (dynamic variables PV, SV, only)
Features supported
-
PROFIBUS PA
Manufacturer ID
11
h
Ident number
1517
h
Device revision
11
h
Profile version
2.0
GSD files
www.products.endress.com/profibus
GSD file version
Output values
Main value, temperature value
Input values
Display value of PLC
Features supported
Device locking: The device can be locked by hardware or
software.
PROFIBUS DP
Manufacturer ID
11
h
Ident number
151F
h
Profile version
2.0
GSD files
www.products.endress.com/profibus
GSD file version
Output values
Main value, temperature value
Input values
Display value of PLC
Features supported
Device locking: The device can be locked by hardware or
software.