Electrical connection
Liquiphant FTL62 Density
18
Hauser
6
Electrical connection
6.1
Required tool
• Screwdriver for electrical connection
• Allen key for screw of cover lock
6.2
Connection requirements
6.2.1
Cover with securing screw
In the case of devices for use in the hazardous area with a certain type of protection, the
cover is sealed by a securing screw.
NOTICE
If the securing screw is not positioned correctly, the cover cannot provide secure
sealing.
‣
Open the cover: slacken the screw of the cover lock with a maximum of 2 turns so that
the screw does not fall out. Fit the cover and check the cover seal.
‣
Close the cover: screw the cover securely onto the housing, making sure that the
securing screw is positioned correctly. There should not be any gap between the cover
and housing.
2 x
0.7 Nm
4
A0039520
13
Cover with securing screw
6.2.2
Connecting protective earth (PE)
When the device is used in hazardous areas, it must always be included in the potential
equalization of the system, irrespective of the operating voltage. This is possible by
connecting to the inner or outer protective ground connection (PE).
6.3
Connecting the device
Housing thread
The thread of the electronics and connection compartment is coated with lubricant
varnish.
Avoid additional lubrication.
6.3.1
2-wire density (electronic insert FEL60D) for density
measurement
NOTICE
Operation with other switching units is not permitted.
Destruction of electronic components.
‣
Do not install the FEL60D electronic insert in devices that were originally used as point
level switches.