Liquiphant FTL62 Density
Mounting
Hauser
17
A0042208
11
Installation in pipes (take fork position and marking into consideration)
Aligning the cable entry
1.
3.
4
3.5 Nm
2.
A0042214
12
Housing with external locking screw and drip loop
The locking screw is not tightened when the device is delivered.
1. Loosen the external locking screw (maximum 1.5 turns).
2. Turn the housing, align the cable entry.
Avoid moisture in the housing, provide a loop to allow moisture to drain off.
3. Tighten the external locking screw.
5.3
Post-mounting check
Is the device undamaged (visual inspection)?
Does the measuring device meet the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature
• Measuring range
Are the measuring point number and labeling correct (visual inspection)?
Is the device adequately protected from wet conditions and direct sunlight?
Is the device properly secured?