6 Commissioning
Levelflex M FMP 40 with Foundation Fieldbus
60
EHauser
bypass / pipe
The "
bypass
/
pipe
" option is designed especially for the installation of probes in a
bypass or a stilling well.
coax probe
Select the "
coax probe
" option when using a coaxial probe. When this setting is made,
the evaluation is adapted to the high sensitivity of the coax probe. This option should,
therefore,
not
be selected when using rope or rod probes.
concrete wall
The "
concrete wall
" option takes into account the signal-damping property of concrete
walls when mounting with < 1 m distance to the wall.
Function "medium property" (003)
This function is used to select the dielectric constant.
Selection:
•
unknown
•
1.4 ... 1.6 (for coaxial probe only)
•
1.6 ... 1.9
•
1.9 ... 2.5
•
2.5 ... 4.0
•
4.0 ... 7.0
•
> 7.0
The lower group applies to very loose or loosened bulk solids.
Reduction of the max. possible measuring range by means of:
•
extremely loose surfaces of bulk solids, e.g. bulk solids with low piled density when
filled pneumatically.
•
Build-up, primarily of moist products.
⇒
Media group
DK (
ε
r)
Typical bulk solids
Typical liquids
Typical measuring
range
0
unknown
1
1,4 … 1,6
– Liquefied gases, e.g. N
2
, CO
2
4 m, coax probe only
2
1,6 … 1,9
– Plastic granules
– White lime, special cement
– Sugar
– Liquefied gas, e.g. propane
– Solvents
– Frigen / freon
– Palm oil
25 m
3
1,9 … 2,5
– Portland cement, plasters
– Mineral oils, fuels
30 m
4
2,5 … 4
– Cereals, seeds
– Ground stone
– Sand
– Benzene, styrene, toluene
– Furan
– Naphthalene
35 m
5
4 … 7
– Naturally-moist (ground) stone, ores
– Salt
– Chlorobenzene, chloroform
– Cellulose spray
– Isocyanate, aniline
35 m
6
> 7
– Metal powder
– Aqueous solutions
– Alcohols
– Ammoniac
35 m