5 Operation
Levelflex M FMP 40 with Foundation Fieldbus
38
EHauser
5.3.3
Factory settings (Reset)
"
Caution!
A reset sets the instrument back to the factory settings. This can lead to an impairment
of the measurement. Generally, you should perform a basic setup again following a
reset.
A reset is only necessary:
•
if the instrument no longer functions
•
if the instrument must be moved from one measuring point to another
•
if the instrument is being de-installed /put into storage/installed
User input (
"
reset
"
(0A3)):
•
33 333= reset of customer parameters
33 333
= reset customer parameters
This reset is recommended whenever an instrument with an unknown 'history' is to be
used in an application:
•
The Levelflex is reset to the default values.
•
The customer specific tank map is not deleted.
•
The mapping can also be deleted in the "
cust. tank map
"
(055)
function of the
"
extended calibr.
"
(05)
function group.
•
A linearisation is switched to "
linear
" although the table values are retained. The table
can be reactivated in the "
linearisation
"
(04)
function group.
List of functions that are affected by a reset
A complete “
basic setup
"
(00)
must be activated.
⇒
•
tank properties (002)
•
medium cond. (003)
•
process proper. (004)
•
empty calibr. (005)
•
full calibr. (006)
•
output on alarm (010)
•
outp. echo loss (012)
•
ramp %span/min (013)
•
delay time (014)
•
safety distance (015)
•
in safety dist. (016)
•
overspill protection (018)
•
brocken probe det (019)
•
end of probe (030)
•
level/ullage (040)
•
linearisation (041)
•
customer unit (042)
•
max. scale (046)
•
diameter vessel (047)
•
check distance (051)
•
range of mapping (052)
•
start mapping (053)
•
delete mapping (055)
•
offset (057)
•
output damping (058)
•
language (092)
•
back to home (093)
•
format display (094)
•
no of decimals (095)
•
sep. character (096)
•
unlock parameter (0A4)
•
application par (0A8)
•
tag no (0C0)