iTHERM TM412
10
Hauser
Terminal head with two cable entries
Plug
2x PROFIBUS
®
PA
2x FOUNDATION™ Fieldbus (FF)
Plug thread
#1
#2
A0021706
M12(#1) / M12(#2)
7/8"(#1) / 7/8"(#2)
7/8"(#1) / 7/8"(#2)
PIN number
1
2
3
4
1
2
3
4
1
2
3
4
Electrical connection (terminal head)
Flying leads
Not connected (not insulated)
3-wire terminal block (1x Pt100)
RD/i
RD/i
WH/i
RD/i
RD/i
WH/i
RD/i
RD/i
WH/i
4-wire terminal block (1x Pt100)
WH/i
WH/i
WH/i
WH/i
WH/i
WH/i
6-wire terminal block (2x Pt100)
RD/BK RD/BK
WH/YE
RD/BK RD/BK
WH/YE
RD/BK RD/BK
WH/YE
1x TMT 4 to 20 mA or HART
®
+/i
i/i
-/i
i/i
+/i
i/i
-/i
i/i
+/i
i/i
-/i
i/i
2x TMT 4 to 20 mA or HART
®
in the
terminal head with a high cover
+(#1)/
+(#2)
-(#1)/
-(#2)
+(#1)/
+(#2)
-(#1)/
-(#2)
+(#1)/
+(#2)
-(#1)/
-(#2)
1x TMT PROFIBUS
®
PA
+/i
-/i
GND/
GND
+/i
-/i
GND/
GND
Cannot be combined
2x TMT PROFIBUS
®
PA
+(#1)/
+(#2)
-(#1)/
-(#2)
+(#1)/
+(#2)
-(#1)/
-(#2)
1x TMT FF
Cannot be combined
Cannot be combined
-/i
+/i
i/i
GND/
GND
2x TMT FF
-(#1)/
-(#2)
+(#1)/
+(#2)
PIN position and color code
1 BN
2 GNYE
3 BU
4 GY
1
4
3
2
A0018929
1 BN
2 GNYE
3 BU
4 GY
1
4
3
2
A0018930
1 BU
2 BN
3 GY
4 GNYE
1
4
3
2
A0018931
Connection combination: insert - transmitter
Insert
Transmitter connection
1)
1x 1-channel
2x 1-channel
2)
1x 2-channel
2x 2-channel
2)
1x Pt100, flying
leads
Pt100 (#1) : transmitter (#1)
Pt100 (#1) : transmitter (#1)
(Transmitter (#2) not
connected)
Pt100 (#1) : transmitter (#1)
Pt100 (#1) : transmitter (#1)
Transmitter (#2) not connected
2x Pt100, flying
leads
Pt100 (#1) : transmitter (#1)
Pt100 (#2) insulated
Pt100 (#1) : transmitter (#1)
Pt100 (#2): transmitter (#2)
Pt100 (#1) : transmitter (#1)
Pt100 (#2) : transmitter (#1)
Pt100 (#1) : transmitter (#1)
Pt100 (#2) : transmitter (#1)
(Transmitter (#2) not
connected)
1x Pt100 with
terminal block
2)
Pt100 (#1) : transmitter in
cover
Cannot be combined
Pt100 (#1) : transmitter in
cover
Cannot be combined
2x Pt100 with
terminal block
2)
Pt100 (#1) : transmitter in
cover
Pt100 (#2) not connected
Pt100 (#1) : transmitter in
cover
Pt100 (#2) : transmitter in
cover
1)
If 2 transmitters are selected in a terminal head, transmitter #1 is installed in the high cover. A TAG cannot be ordered for the 2nd transmitter as
standard. The bus address is set to the default value and, if necessary, must be changed manually before commissioning.
2)
Only in the terminal head with a high cover, only 1 transmitter possible. A ceramic terminal block is automatically fitted on the insert.