Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
Commissioning
Hauser
31
5.
Setup → Tube diameter
(only for "Tank type" = "Bypass / pipe")
Specify the diameter of the bypass or stilling well.
6.
Setup → Tank level
Specify the filling level (
Partially filled
or
Fully flooded
)
7.
Setup → Distance to upper connection
In bypasses: Specify the distance from the reference point R to the lower edge of the
upper outlet; in all other cases, keep the factory setting
8.
Setup → DC value
Specify the dielectric constant of the upper medium
9.
Setup → Empty calibration
Specify the empty distance E (distance from the reference point R to the 0% mark).
10.
Setup → Full calibration
Specify the full distance F (distance from the 0% mark to the 100% mark).
11.
Setup → Level
Displays the measured level L
L
.
12.
Setup → Interface
Displays the interface height L
I
.
13.
Setup → Distance
Displays the distance D
L
between the reference point R and the level L
L
.
14.
Setup → Interface distance
Displays the distance D
I
between the reference point R and the interface L
I
.
15.
Setup → Signal quality
Displays the signal quality of the analyzed level echo.
16.
Setup → Mapping → Confirm distance
Compare the distance displayed with the actual value to start recording an
interference echo map.