Commissioning
Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
30
Hauser
8.3.2
Configuring interface measurement
An interface measurement is only possible if the device has the corresponding software
option. In the product structure: feature 540 "Application Package", option EB "Interface
measurement".
D
L
L
L
F
L
I
UP
D
I
LN
E
R
0%
100%
DK (DC )
2
2
DK
DC
1
1
(
)
A0011177
11
Configuration parameters for interface measurement
R = Reference point of measurement
D
I
= Interface distance (distance from flange to DK
2
)
E = Empty calibration (= zero point)
L
I
= Interface
F = Full calibration (= span)
D
L
= Distance
LN = probe length
L
L
= Level
UP = Measured thickness upper layer
1.
Setup → Device tag
Enter device tag.
2.
Setup → Distance unit
Select the length unit.
3.
Setup → Operating mode
Select
Interface
option.
4.
Setup → Tank type
Select tank type.
3)
Only available in devices with the "Interface measurement" application package