DTT31, DTT35
Maintenance
Hauser
25
5.2.2
Hints for the configuration with ReadWin
®
2000
Comprehensive information on the ReadWin
®
2000 configuration software may be found in the
Operating Instructions BA137R/09/en.
5.2.3
Hints for the configuration with FieldCare
FieldCare is an universal configuration software based on FDT/DTM technology.
!
Note!
• To configure the Flowphant
®
T DTT31/35 with FieldCare the “PCP (ReadWin)
Communication DTM” and the Flowphant Device-DTM are required.
• The device supports only offline configuration and up-/download of parameters. The online
configuration is not supported.
Detailed information concerning FieldCare may be found in the operation manual (BA027S/c4)
or see: www.endress.com.
6
Maintenance
Any buildup on the sensor can have a negative effect on the accuracy. For this reason, check the
sensor for buildup at regular intervals.
"
Caution!
Make sure the process is unpressurized before you remove the device! Do not twist the device
out of the process connection thread at the housing. Always use a suitable open-ended wrench
for disassembly work (see also
→
Fig. 5) (
→
Chap. 3.3.1).
7
Accessories
All dimensions in the drawings are given in mm (inch).
7. 1 Welding bosses and coupling
7.1.1
Welding boss with sealing taper
Collar welding boss moveable with sealing taper
and pressure screw;
material of parts in contact with the process:
316L, PEEK,
Max. process pressure 10 bar (145 psi)
Order number: 51004751
T09-TSM470AX-06-09-00-en-000