Installation
Flowfit CYA27
24
Hauser
Connecting cable
Green (GN)
DIO module, port 1, terminal 48
Distributor terminal (3)
Distributor terminal (4)
not connected
5.4.2
Settings on the CM44x
Activating the binary input of the flow switch
1. Go to
Menu/Setup/Inputs/Binary input x:1
and enable
Binary input
.
2. Set
Signal type: Static signal, Signal level: Low
.
3. Assign a limit contactor to the binary input in:
Menu/Setup/Basic setup/Limit
switches
with the options
Source of data: Binary input x:1, Operating mode:
Above limit check, Function: On
Activating the relay for the status indication light
Depending on the relay used, the following options can be used to activate the connected
relay:
•
Alarm relay:
No action necessary if the alarm relay has already been activated and the
following has been configured:
Function: Diagnostics, Operating mode: Namur F
•
2R/4R module:
Menu/Setup/Basic setup/Relay x:1
, settings:
Function
:
Diagnostics
,
Operating mode
:
Namur F
When using the alarm relay, it is no longer available for other messages.
Activation/assignment of flow switch for status indication light
‣
Reconfigure the diagnostic message for the limit contactor (S910) in
Menu/Setup/
Basic setup/Diagnostics settings/Diag. behavior/S910 Limit switches/Status
signal/Failure (F)
.
The status of the limit contactor and thus the flow rate in the assembly is available
as a process value for all outputs of the transmitter. As soon as the flow rate is
insufficient,
F910 Limit switches
is displayed on the device along with a red screen
and a red status indication lamp on the assembly.
Any other error on the transmitter that results in a red screen will also result in a red
status display on the assembly.
The status indication light indicates the flow status only if the flow switch was also
ordered. The status indication light on its own can also be used for the NAMUR status
of the measuring system (transmitter and connected measuring devices/sensors).
Содержание Flowfit CYA27
Страница 2: ......
Страница 49: ......
Страница 50: ......
Страница 51: ......
Страница 52: ...www addresses endress com 71511599 71511599 ...