Configuration and online parameterization
FieldPort SWA50
60
Hauser
Parameter
Description
Burst Command Number Prerequisite
Burst mode: On
Description
Select the burst command number. Description of burst command: → 60. For
additional information, see the HART Specification.
Selection/user entry
• Device Index "SWA50": Select 3, 9 or 48 from a dropdown list
• Device Index "Connected field device": Enter 1, 2, 3, 9, 33 or 48
Factory setting
1
Additional information
• You can configure any commands you wish for connected field devices. Refer to
the appropriate Operating Instructions for further details.
• Use command 3 and 48 if in doubt.
Device Variable Code 0
to
Device Variable Code 7
Prerequisite
• Burst mode: On
• Burst command number: 9 or 33
Description
Select the device variables that are transmitted with the burst message.
Selection/user entry
• Device Index "SWA50": Device variable code from dropdown list
• Device Index "Connected field device": Enter device variable code
Factory setting
250
Additional information
Refer to the documentation of the field device for the device variables of the
connected field device.
Description of the burst command for the FieldPort SWA50
Burst command
Description
3
Transmits the value of the 4 to 20 mA signal and up to 4 pre-defined device
variables and the associated unit. Device variables: First variable, second variable,
third variable and fourth variable.
9
The
Device Variable Code 0
to
Device Variable Code 7
fields are enabled.
Transmits the value, the unit and the status of up to 8 device variables.
48
Transmits the additional device status.
Description of the burst command for the field device connected to the FieldPort
Burst command
Description
1
Transmits the value and the unit of the "First Variable".
2
Transmits the value of the 4 to 20 mA signal and the corresponding value as a
percentage, e.g. 4 mA and 0 % or 12 mA and 50 %.
3
Transmits the value of the 4 to 20 mA signal and up to 4 pre-defined device
variables and the associated unit. Device variables: First variable, second variable,
third variable and fourth variable.
9
The
Device Variable Code 0
to
Device Variable Code 7
fields are enabled.
Transmits the value, the unit and the status of up to 8 device variables.
33
The
Device Variable Code 0
to
Device Variable Code 3
fields are enabled.
Transmits the value and the unit of up to 4 device variables.
48
Transmits the additional device status.