Maintenance and cleaning
CE 4
24
Hauser
1.
Select the option 'Set Param' in the set-up menu: Keys
V
or
W
2.
Operate the ’OK’ key. LOGO! displays the first paramete.
Pos. A: Block number
Pos. B: Display number on functions when using more than one display (not
relevant here)
Pos. C: The preset value of the parameter T (time)
Pos. D: Actual value
’ESC’ leads to a return to the set-up menu without changes.
3.
Select the required parameter: Keys
V
or
W
.
4.
If a parameter is to be changed then select that parameter and operate the ’
OK
’
key.
5.
Using the keys
U
or
T
´the cursor can be moved to the point in the parameter that
is to be changed. Using the keys
V
or
W
the value can be changed.
6.
Accept the new set-up using the ’
OK
’ key.
7.
Return to ’Continuous operation’ by operating the ’
ESC
’ key twice.
LOGO! switch to RUN
LOGO! can be switched to RUN using the main menu.
1.
Return to main menu: ’
ESC
’ key
2.
Move ’
>
’ to ’
Start
’: Keys
V
or
W
3.
Accept ’Start’: ’
OK
’ key
Function
Set up position
Time interval
Factory default
Start hose rinse
B01
(0...99h)
24h
Hose rinse time
B02
(0...99s)
45s
Pump rinse time
B03
(0...99s)
30s
Start sensor rinse
B04
(0...99h)
18h
Post rinse
B05
(0...99s)
10s
Clean (detergent)
B06
(0...99s)
30s
Pre-rinse
B07
(0...99s)
10s
Hold time after suction hose rinse
B08
(0...99s)
20s
Pump status
Hold (transmitter)
Stop
>Set Param
Set Clock
Prg Name
B1
1
T
=60:00s
Ta
=06:00s
B
C
D
A