TECHNICAL DATA
146
smart Econ - emz-HCW - 180116
Flow/return contact temperature sensor
Sensor type
Pipe-mounted sensor
Temperature limit
up to 90°C temperature resistant
Connection cable
PVC, 2.5 m long
Characteristic curve and resistance values of PT1000 temperature sensors
-40 °C
0.85 k
Ω
0 °C
1.00 k
Ω
40 °C
1.15 k
Ω
90 °C
1.35 k
Ω
-30 °C
0.88 k
Ω
5 °C
1.02 k
Ω
50 °C
1.19 k
Ω
100 °C
1.39 k
Ω
-20 °C
0.92 k
Ω
10 °C
1.04 k
Ω
60 °C
1.23 k
Ω
110 °C
1.42 k
Ω
-10 °C
0.96 k
Ω
20 °C
1.08 k
Ω
70 °C
1.27 k
Ω
120 °C
1.46 k
Ω
-5 °C
0.98 k
Ω
30 °C
1.12 k
Ω
80 °C
1.31 k
Ω
130 °C
1.50 k
Ω
0.70 k
Ω
0.80 k
Ω
0.90 k
Ω
1.00 k
Ω
1.10 k
Ω
1.20 k
Ω
1.30 k
Ω
1.40 k
Ω
1.50 k
Ω
1.60 k
Ω
-40 ˚C
-20 ˚C
0 ˚C
20 ˚C
40 ˚C
60 ˚C
80 ˚C
100 ˚C
120 ˚C