DEVICE CONFIGURATION
112
smart Econ - emz-HCW - 180116
• Select a heating circuit, e.g. ›HEAT CIRCUIT 1‹ .
Make the settings for the other heating circuits accordingly.
(Example, depending on the selected system)
• Change whether or not the global set points for this heating circuit are to be used, if necessary.
- ›use global day temp‹: Setpoint temperature for heating times
- ›use global eco temp.‹: Setpoint temperature for setback times
- ›weather guidance‹: After connecting a room controller, 100% room control can be set here.
- ›show room temperature‹: Display room temperature in overview mode (without room controller)
- ›pump continuously‹: Outdoor temperature-dependent pump operation
- ›pump on day ot °C‹: If the outdoor temperature in daytime operation is below the set tempera-
ture, the pump is switched on.
- ›pump on night ot °C‹: If the outdoor temperature in night mode is below the set temperature,
the pump is switched on.
• Select ›ROOM SETPOINTS‹.
- Setting of switching times and room temperatures (local)
“Setting heating periods and temperatures” on page 31
HEAT CIRCUIT 1
^
use global day temp.:
NO
use global eco temp.:
NO
ROOM SETPOINTS
w eather guidance:
YES
show room temperature
NO
pump continously
YES
pump on day ot °C
22
pump on night ot °C
16
i
BACK