Configuring room temperature influence on the heating curve
(heating circuits without mixer)
• For example, select ›HEAT CURVE‹ in the ›HEAT CIRCUIT 1‹ menu.
(Example, depending on the selected system)
• Change the parameters if necessary.
- Heating curve:
›set point at <1>°‹: Flow set point of the heating curve at P1 (-20°C) (setting range: P2 - 99)
›set point at <2>°‹: Flow set point of the heating curve at P2 (-5°C) (setting range: P3 - P1)
›set point at <3>°‹: Flow set point of the heating curve at P3 (+5°C) (setting range: P4 - P2)
›set point at <4>°‹: Flow set point of the heating curve at P4 (+20°C) (setting range: 0 - P3)
P1 to P4 see ›BASE OT HEAT CURVE‹ menu “Change heating curve” on page 113
Room temperature influence:
The flow temperature is adjusted according to the set point
deviation of a room.For example, if it is 'much too cold' in this room, the flow temperature is
increased.The extent to which the flow temperature changes is calculated from the parameter
'Gain' given below.
›gain room influence‹: (Flow temperature change per °C deviation from room temperature)
HEAT CURVE
^
current set point (°C)
0
shift heating curve
0.0
minimum supply temp. (°C)
20
maximum supply temp. (°C)
65
set point at <1>°:
60
set point at <2>°:
53
set point at <3>°:
44
set point at <4>°:
23
i
interval (sec)
30
Amplification (0.1Sec/K)
20
HEAT CURVE
^
gain room influence
4
room influence limit (K)
25
economy mode
0
BACK
i