4-20mA outputs
Reference Drawing # 1131
The Model EMS1304 comes with two 4-20mA outputs. The ranges are set during final test to the information
supplied by the customers.
Maximum output Loop compliance is 800 Ohms.
AOUT1 (instantaneous opacity, zero/span when in check mode) is connected at Control unit terminals 11 & 12
and supplies the opacity signal to a recorder or DAS and too the service module 14 & 13 (on TB1, - 1101) for
display at the sensor location.
AOUT 2 (average opacity, zero/span when in check mode) is connected at Control unit terminals
13 & 14
.
No calibration is necessary; however if you want to check that other devices such as recorders or DAS are
responding correctly use the following procedure.
Recorder or other device calibration:
On the control unit front panel press the AUTO/MAN key for a maintenance zero and span cycle. Both outputs
will correspond to the opacity display value.
(+) Recorder/DAS (-)
14
11+
13
12-
Sensor location
terminal TB 1
EMS1304 Control
unit rear panel
terminals
Содержание 1304
Страница 45: ...44 Section 8 DRAWINGS ...
Страница 46: ...45 EMS 1001 Mounting under 6 STACK ...
Страница 47: ...46 EMS 1002 Mounting over 6 stack ...
Страница 48: ...47 EMS 1024 Air purge Weather cover mech Installation ...
Страница 49: ...48 EMS 1078 PANEL cut out for 1304 control unit ...
Страница 50: ...49 EMS 1079 1304 control unit dimensions ...
Страница 51: ...50 EMS 1077 Terminal identification 1304 control unit ...
Страница 52: ...51 EMS 1131 1304 with recorder system wiring ...
Страница 54: ...53 EMS1101 Sht 1 of 3 Dual Blower system wiring ...
Страница 55: ...54 EMS 1101 Sht 2 of 3 Single Blower system wiring ...
Страница 56: ...55 EMS 1101 Sht 3 of 3 Without Blower system wiring ...