25
Section 4
INSTRUMENT OPERATIONS AND ADJUSTMENTS
Overview of the systems operation
The Model 1304 Opacity monitor system consists of transceiver, retro reflector, service module and the control
unit. The maintenance module has a digital display for reading opacity from the control unit and T2 from the
transceiver. It also has connections for attaching a meter for trouble shooting or calibration when necessary. Other
switches are provided for initiating zero and span modes during service or maintenance. If any switch causes the
system to read other than stack opacity the Control unit Fault Alarm system will be energized notifying the
operator. A fault output signal (open transistor collector) is also energized for use with other alarms or DAS
system, which need to know opacity readings are not representative of the actual stack opacity and a fault
condition exists.
Only two conditions are considered normal operation
; 1- Reading smoke, 2- Computer or internal clock
initiated calibration check cycle.
Front Panel LED's
ALARM
-
Red LED is blinking when a Fault is detected. Manual Cal.
RUN
-
Green LED is on during normal operation and blinking if system is in S/M mode. The primary reason for
S/M mode is to prevent 4-20mA outputs from changing when user is modifying block ware.
OPERATE
-
Red LED is on during normal operation.
AUTO/MAN
-
Red LED is on during calibration check mode.
ZERO
-
Red LED is on when zero cal cycle is in progress, out during span or normal operation.
SPAN
-
Red
LED is on when span cal cycle is in progress, out during zero or normal operation.
HIGH OPACITY
- Red LED is on if opacity exceeds set point for more than the time delay (typically 30 seconds).
REM/LOC
-
Red LED always out this is not used.
Fault Messages
Air purge low
-
Airflow to the transceiver and/or retro reflector is not sufficient.
No Stack Power
-
Indicates loss of service module power loss or other related power or component failure from
the service module.
T2 4-20 Lost/low
- Transceiver 4-20mA current loop is out of specification or missing.
Maintenance Mode
-
Indicates a maintenance mode switch on the service module is in a position and the system
is not displaying or outputting the smoke reading.
Window Dust
-
Dirt has accumulated on the transceiver lens and/or the zero mirror in excess of the > 5% limit
and must be cleaned.
Zero Cal Fail
-
During calibration check the zero reading has exceeded the > 2% opacity set point.
Span Cal Fail
-
During calibration check the span reading has exceeded the > 2% opacity set point
Manual Cal
-
A manual calibration check from the control unit front panel AUTO/MAN key was pressed.
Содержание 1304
Страница 45: ...44 Section 8 DRAWINGS ...
Страница 46: ...45 EMS 1001 Mounting under 6 STACK ...
Страница 47: ...46 EMS 1002 Mounting over 6 stack ...
Страница 48: ...47 EMS 1024 Air purge Weather cover mech Installation ...
Страница 49: ...48 EMS 1078 PANEL cut out for 1304 control unit ...
Страница 50: ...49 EMS 1079 1304 control unit dimensions ...
Страница 51: ...50 EMS 1077 Terminal identification 1304 control unit ...
Страница 52: ...51 EMS 1131 1304 with recorder system wiring ...
Страница 54: ...53 EMS1101 Sht 1 of 3 Dual Blower system wiring ...
Страница 55: ...54 EMS 1101 Sht 2 of 3 Single Blower system wiring ...
Страница 56: ...55 EMS 1101 Sht 3 of 3 Without Blower system wiring ...