Warnings
1.
When the photovoltaic (PV) array is exposed to light, it supplies a d.c. voltage to the PCE.
2.
External RCD Type A 30mA is required on backup port (if connected).
3.
An RCD is not permitted on the grid/supply side of the device
as it is a multi-mode inverter and
an RCD would allow disconnection of the neutral MEN connection for backup loads.
4.
It is required that any PV modules connected to the device have an IEC 61730 Class A rating.
5.
If the equipment is used in a manner not specified by the manufacturer, the protection provided
by the equipment may be impaired.
6.
Only a qualified professional (e.g. service person) may install the Elektrobank 14.
7.
Servicing or replacement of batteries shall not be conducted in the field by anyone other than
Empower personnel. Initial installation is allowed as per this manual.
8.
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
9.
CAUTION: Do not open or damage batteries. Released electrolyte is harmful to the skin and eyes.
It may be toxic.
10.
CAUTION: The backup port should not be used for devices providing safety or health critical
devices
11.
SAFE HANDLING: Elektrobank 14 and battery modules are heavy. To minimise risk when handling
the goods, lift and transport the goods carefully and wear personal protective equipment such as
steel-toe boots and gloves. Use of lifting equipment is recommended
12.
SAFE TRANSPORT: Always transport the goods to site in the original packaging. During unpacking,
inspect the goods for damage such as large dents or deep scratches, which may indicate the unit
was dropped. Do not use Elektrobank 14 if it is defective or appears damaged in any way,
internal or external. Contact your supplier for further advice.
13.
Touch current is above the limit. Ensure 10mm2 copper PE cable is used for connection to PE
terminal.
14.
The Elektrobank 14 cannot be used in multiple inverter combinations as per section 5 of the
AS/NZS 4777.2:2020.