Version
5.0
Page 17 of 33
1.
Bolts shall be seated and loaded to 0.5Nm int the following pattern, starting from the middle bolt
2.
The bolts shall then be tightened to 1Nm in the same pattern
8
Wiring
In addition to all requirements in this document, ensure all wiring conforms to AS/NZS 3000 and AS/NZS
4777.1 for Australia.
Connection Summary:
Connection Name
Connection Type
DVC Class
PV
4 Sunclix External Connectors
DVC-C
Grid
2 x 6mm
2
minimum Live and Neutral into terminal block
DVC-C
Backup
2 x 4mm
2
minimum Live and Neutral into terminal block
DVC-C
Earth
Either a) or b) below
a)
Single earth cable made of copper and 10mm
2
or greater
(but less than 16mm
2
), into ‘Grid’ terminal
b)
One 6mm
2
minimum earth cable into ‘Grid’ terminal
block and a second earth cable into ‘Backup’ terminal
block, of the same cross sectional area
DVC-A
LAN
RJ45
DVC-A
DRM0
2 wires into terminal block
DVC-A
Meter RS485
2 wire twisted pair into terminal block
DVC-A
Table 1 - Connection Summary
8.1
External Isolation Device Requirements
The following isolation devices are required
1.
40A single pole circuit breaker for grid port, connected to active conductor only