Installation shall follow and comply with AS 5139, AS 3000 as well as any requirements
from this manual.
1.
Find a suitable mounting location as per AS 5139
•
a risk assessment for the mounting location shall be completed
2.
The Elektrobank 14 can be mounted on a wall with the wall mount kit or floor standing, with the
addition of the floor mount kit.
•
The wall mount bracket shall always be used
•
The wall shall always be capable of taking the full weight of the unit, whether wall
mount or floor standing.
3.
Mounting Location
•
The Elektrobank 14 is rated to IP66 so can be mounted inside or outside
•
Do not mount the Elektrobank 14 in a location with direct sunlight. Outdoor suggested
(but not limited to) locations include:
i.
Under an awning
ii.
On a South Facing wall
•
Ensure no animals or insects are likely to be able to nest close to the unit.
•
No plants can be growing inside 1m radius from the mounting location
•
Ensure there are no obstructions (to ensure adequate ventilation) inside the dimensions
from Figure 1, including, but not limited to:
i.
Wall, floor, Ceiling/roof
ii.
Any other devices or equipment
iii.
Vents to any wall or other structure
iv.
Any Heat sources
•
No heat source should be within the clearance limits indicated or below the unit at any
distance
•
Installation position shall not prevent access to disconnection means.
•
If indoor mounted,
i.
a fire alarm is required to be installed in the same room as the Elektrobank 14
ii.
The room should have at minimum one external wall vent
0.6m
minimum
0.3m minimum
1.5m
minimum
0.9m minimum
0.6m minimum
Figure 2 - Clearance around unit