Empire Heating Systems FAW-55-1SPP Скачать руководство пользователя страница 4

32192-1-0314

Page 4

Ventilation and Combustion Air

Wall furnaces shall be installed in a location in which the facilities 

for ventilation permit satisfactory combustion of gas and proper 

venting under normal conditions. In buildings of conventional 

frame, brick, or stone construction without tight storm windows 

and doors, infiltration is normally adequate to provide air for com

-

bustion and draft hood dilution.

Where appliances are installed in confined and unconfined 

spaces within a building, the building being of unusually tight 

construction, air for combustion and ventilation must be obtained 

directly from outdoors or from such spaces that freely communi-

cate with the outdoors. Under these conditions, the confined and 

unconfined spaces shall be provided with two permanent open

-

ings, one near the top of the enclosure and one near the bottom; 

each opening shall have a free area of not less than one square 

inch (6.45cm

2

) per 2,000 BTU hr. (.6KW/H) of total input.

Qualified Installing Agency

Installation and replacement of gas piping, gas utilization equip-

ment or accessories and repair and servicing of equipment shall 

be performed only by a qualified agency. The term “qualified 

agency” means any individual, firm, corporation or company 

which either in person or through a representative is engaged 

in and is responsible for (a) the installation or replacement of 

gas piping or (b) the connection, installation, repair or servicing 

of equipment, who is experienced in such work, familiar with all 

precautions required and has complied with all the requirements 

of the authority having jurisdiction. 

State of Massachusetts: 

The installation must be made by a 

licensed  plumber  or  gas  fitter  in  the  Commonwealth  of  Mas

-

sachusetts.

The installation must conform with local codes or, in the absence 

of local codes, with the National Fuel Gas Code, ANSI Z223.1/

NFPA 54* Natural Gas and Propane Installation Code, CSA 

B149.1.

*Available from the American National Standards Institute, Inc., 

11 West 42nd St., New York, N.Y. 10036.

Clearances

1.  In selecting a location for installation , it is necessary to provide 

adequate accessibility clearances for servicing and proper 

installation.

2.  The FAW-55 can be attached to the wall or recessed into the 

wall up to 4 inches (102mm) in depth.

3.  The wall in which the furnace is recessed has (0) zero (0mm) 

clearance to the furnace sides and top.

4.  When using side discharge registers, SOR-1 or SOK-1, the 

furnace cannot be recessed into the wall.

5.  Clearance to sidewall or combustible material is 4 inches 

(102mm).

6.  Ceiling clearance is 7 1/2 inches (191mm)

7.  Floor and rear wall clearance is (0) zero inches (0mm).

8.  Clearance of 18 inches (457mm) is required to adjacent wall 

or combustible material when flushed mounted SOR-1, side 

outlet register is used.

Before Installing Consider The Following Venting

1.  A chimney for residential-type or low-heat gas utilization equip-

ment shall extend at least 3 feet (914mm) above the highest 

point where it passes through a roof of a building and at least 

2 feet (610mm) higher than any portion of building within a 

horizontal distance of 10 feet (3m).

2.  This furnace must not be connected to a chimney flue serving 

a separate solid-fuel burning appliance.

3.  Uninsulated Single-Wall Metal Pipe shall not be used outdoors 

in cold climates for venting gas utilization equipment.

4.  Attention! This Fan Type Vented Wall Furnace is equipped with 

a vent safety switch. In the event of spillage of flue products 

due to improper venting the vent safety switch will open, which 

results in the main burners to “shut off.”

Refer to Figure 1 and Page 12 for additional information regarding 

U.L. Listed gas vent equipment.

Installing Optional Side Outlets

Side outlet register, SOR-1 may be installed on one or both sides 

of the furnace at the required clearances of 18 inches (457mm) to 

adjacent wall or combustible material as shown in Figure 2.

1.  Locate and cut the 5 1/2” (140mm) square opening in the cabinet 

side using the template from the kit, exposing the inner liner 

knock-out.

2.  Remove the knock-out.

3.  Place the register on the 5 1/2” (140mm) opening with the 

louvers set for the desired direction and mark the mounting 

holes using the register as a template.

4.  Drill two (2) 1/8” (3mm) diameter holes in cabinet side and 

fasten the register in place with two (2) #10 x 1” (25mm) screws 

provided.

Side outlet kit, 10” (254mm) boot assembly with register, SOK-1 for 

warm air discharge into an adjoining room may be installed on either 

side of the furnace at the required clearance of 4 inches (102mm) 

to adjacent wall as shown in Figure 3A.

1.  Locate and cut the 5 1/2” (140mm) square opening in the cabinet 

side using the template from the kit, exposing the inner liner 

knock-out.

2.  Remove the knock-out.

3.  Using the inner and outer boots as hole templates, mark and 

drill (8) 1/8” (3mm) diameter holes in the inner liner and cabinet 

side.

4.  Using Figure 3A locate and cut a 6 3/4” (171mm) square open-

ing through walls.

5.  Attach furnace to wall (see 

Attaching Furnace to Wall

).

6.  With furnace in place, after checking alignment of side outlet 

opening in wall and furnace, place the 9 3/8” x 9 3/8” (238mm 

x 238mm) side outlet wall plate over outer boot, pass the outer 

boot through the wall and attach side outlet wall plate to furnace 

side of wall with (2) #10 x 1” (25mm) screws provided.

7.  Fasten outer boot to the cabinet side with (4) #8 x 1/4” (6mm) 

screws provided.

8.  Position and attach inner boot to inner liner with (4) #8 x 1/4” 

(6mm) screws provided.

9.  Locate the register with its louvers positioned for the desired 

air discharge direction and mark the mounting holes using the 

register as a template.

10.Drill (2) 1/8” (3mm) diameter holes in the wall and fasten the 

register in place with (2) #10 x 1” (25mm) screws provided.

Installing Optional Rear Outlet

Rear outlet kit, 10” (254mm) boot assembly with register, ROK-1 

for warm air discharge into an adjoining room.

Attention:

 Before furnace is attached to the wall, the wall opening 

for the rear outlet must be cut, in addition to removal of the outer 

and inner casing knockouts on furnace.

1. The wall opening measurements for the rear outlet are the 

following.

  A.  From floor to bottom of wall opening is 14 3/4” (375mm).

  B.  From the bottom of wall opening to top of wall opening is 

8 1/2” (216mm).

  C.  Wall opening width is 12 1/8” (308mm).

2.  Remove outer casing knockout from outer casing back.

3.  Remove inner casing knockout from inner casing.

4.  Attach furnace to wall (see 

Attaching Furnace to Wall

).

5.  Align clearance holes on 8” x 12” (203mm x 305mm) boot with 

Содержание FAW-55-1SPP

Страница 1: ...these instructions are not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in...

Страница 2: ...burner ignition devices are located not less than 18 457mm above the floor Such equipment shall be located or protected so it is not subject to physical damage by a moving vehicle Specifications Model...

Страница 3: ...gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clo...

Страница 4: ...onnected to a chimney flue serving a separate solid fuel burning appliance 3 Uninsulated Single Wall Metal Pipe shall not be used outdoors in cold climates for venting gas utilization equipment 4 Atte...

Страница 5: ...connec tion Also refer to Figure 2 for positioning the furnace on wall and for locating gas line connection Locating Gas Supply The gas line can enter the furnace either though the floor or wall The...

Страница 6: ...air in the gas line it is suggested that a match be used The match will light the pilot faster than the piezo under this condition Attention The 7 8 22mm strain relief bushing is located within the s...

Страница 7: ...will be blue extending past the thermocouple The flame will surround the thermocouple just be low the tip Natural gas pilots require adjusting when the inlet gas pressure is above 5 w c 1 245kPa Remov...

Страница 8: ...Fan Motor The upper front panel the shroud sur rounding the fan blade and fan blade must be removed See oiling the Motor paragraph on page 7 Spark Igniter Does Not Light Pilot With air in the gas lin...

Страница 9: ...knob clockwise to OFF 6 Wait ten 10 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to...

Страница 10: ...808 PILOT TUBING 25 DV562 LOWER FRONT PANEL 26 DV824 FRONT BURNER 27 P8842 MAIN BURNER ORIFICE NATURAL GAS TWO REQUIRED 27 P8853 MAIN BURNER ORIFICE LP GAS TWO REQUIRED 28 DV687 MANIFOLD AND PLATE ASS...

Страница 11: ...32192 1 0314 Page 11...

Страница 12: ...oval elbows 3 Single story type B 1 gas vents require a baseplate and one pair of ceiling plate spacers 4 Multi story type B 1 gas vents require a baseplate one pair of ceiling plate spacers at the fi...

Страница 13: ...ranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numb...

Страница 14: ...32192 1 0314 Page 14 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...

Страница 15: ...A bill of sale cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might r...

Страница 16: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Страница 17: ...tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareil Ne touchez a aucun interrupteur Ne pas vous servir des t l phones se trouvant dans le b ti ment o vous...

Страница 18: ...syst me de com mande et les commandes de gaz qui ont t en contact avec l eau Ce radiateur ne doit pas tre branch une chemin e servant un autre appareil br lant un combustible solide A cause des hautes...

Страница 19: ...que les pompiers vous assurent de la s ret de ces endroits avant d y aller Utiliser le t l phone de votre voisin et appeler les pompiers et une personne entra n e avec le propane Ne pas ouvrir les so...

Страница 20: ...tall s dans un endroit o la facilit delaventilationpermetunecombustiondegazsatisfaisanteetun chappe ment convenable sous des conditions normales Dans les b timents de construction conventionnelle de b...

Страница 21: ...tant est chang de place Un guide est fourni dans l emballage du radiateur pour vous aider localiser la connexion pour la ligne de gaz Aussi r f rer la Figure 2 pour positionner le radiateur sur le mur...

Страница 22: ...de 3 914mm du compartiment des contr les au bas du radiateur 2 Enlever l entr e d fon able de 7 8 22mm du c t du panneau ap propri 3 Introduire le bouchon de nylon de l assemblage de la fiche de 3 914...

Страница 23: ...que le radiateur ait fonctionn il se peut que les ouvertures du br leur soient bloqu es par des mati res trang res venant de l air de combustion Donc un nettoyage du br leur peut tre exig pour obteni...

Страница 24: ...ation lequel doit tre install et entretenu correctement ou lorsque vous tripotez avec le syst me de fermeture de s ret de l vent peut causer un empoissonnement au monoxide de carbone CO et possiblemen...

Страница 25: ...tion La veilleuse est suppos e rester allumer Si elle s teint recommencer les tapes 5 jusqu 10 Si le bouton ne revient pas sa position lorsque vous le rel chez arr ter et appeler imm diatement un tech...

Страница 26: ...intervalles jusqu ce qu elle s allume Si l lectrode ne Produit Pas d tincelle 1 V rifier les connexions des fils lectriques 2 V rifier la distance du br leur de la veilleuse au bout de l lectrode Doi...

Страница 27: ...s ret de l vent 16 8720130 Manchon 17 11765 Assemblage du compartiment d interrupteur 18 DV 832 Couvercle du compartiment d interrupteur 19 912073 Contr le de tol rance 20 R 1941 Contr le du ventilat...

Страница 28: ...12428 7 0314 Page 12 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62222 0529...

Страница 29: ...de base et une paire d entretoises pour la plaque du plafond 4 Les vents gaz de type B 1 pour plus d un tage exige une plaque de base une paire d entretoises pour la plaque du pla fond au plafond du...

Страница 30: ...mages pouvant r sulter de l emploi de l emploi abusif ou d une installation incorrecte de cet appareil Frais de d placement de diagnostic et de transport des pi ces sous garantie vers et depuis l usin...

Отзывы: