REqUIREMENTS FOR MASSACHUSETTS

For all side wall horizontally vented gas fueled equipment installed 

in every dwelling, building or structure used in whole or in part for 

residential  purposes,  including  those  owned  or  operated  by  the 

Commonwealth and where the side wall exhaust vent termination 

is less than seven (7) feet above finished grade in the area of the 

venting, including but not limited to decks and porches, the following 

requirements shall be satisfied:

1.  INSTaLLaTION OF CaRBON MONOXIDe DeTeCTORS. at 

the time of installation of the side wall horizontal vented gas fu

-

eled equipment, the installing plumber or gasfitter shall observe 

that a hard wired carbon monoxide detector with an alarm and 

battery back-up is installed on the floor level where the gas 

equipment is to be installed. In addition, the installing plumber 

or gasfitter shall observe that a battery operated or hard wired 

carbon monoxide detector with an alarm is installed on each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services 

of qualified licensed professionals for the installation of hard 

wired carbon monoxide detectors

 

a.  In the event that the side wall horizontally vented gas fu

-

eled equipment is installed in a crawl space or an attic, 

the hard wired carbon monoxide detector with alarm and 

battery back-up may be installed on the next adjacent floor 

level.

 

b.  In the event that the requirements of this subdivision can not 

be met at the time of completion of installation, the owner 

shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said 

thirty (30) day period, a battery operated carbon monoxide 

detector with an alarm shall be installed.

2.  aPPROVeD CaRBON MONOXIDe DeTeCTORS. each carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified. 

3.  SIGNAGE. A metal or plastic identification plate shall be per

-

manently mounted to the exterior of the building at a minimum 

height  of eight  (8)  feet above  grade  directly  in  line  with  the 

exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY 

BELoW. KEEP CLEAR oF ALL oBStRUCtIonS”.

4.  INSPeCTION. The state or local gas inspector of the side wall 

horizontally  vented  gas  fueled  equipment  shall  not  approve 

the installation unless, upon inspection, the inspector observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

 

(b)  EXEMPTIONS: The following equipment is exempt from 

248 CMR 5.08(2)(a)1 through 4: 

 

 

1.  The equipment listed in Chapter 10 entitled “Equip

-

ment Not Required To Be Vented” in the most current 

edition of NFPa 54 as adopted by the Board; and 

 

 

2.  Product Approved side wall horizontally vented gas 

fueled equipment installed in a room or structure 

separate from the dwelling, building or structure used 

in whole or in part for residential purposes. 

 

(c)  MANUFACTURER REQUIREMENTS - GAS EQUIPMENT 

VeNTING SYSTeM PROVIDeD. When the manufacturer of 

Product Approved side wall horizontally vented gas equip

-

ment provides a venting system design or venting system 

components with the equipment, the instructions provided 

by the manufacturer for installation of the equipment and 

the venting system shall include:

 

 

1.  Detailed instructions for the installation of the venting 

system design or the venting system components; and

 

 

2.  a complete parts list for the venting system design or 

venting system. 

 

(e)  A copy of all installation instructions for all Product Approved 

side  wall  horizontally  vented  gas  fueled  equipment,  all 

venting instructions, all parts lists for venting instructions, 

and/or all venting design instructions shall remain with the 

appliance or equipment at the completion of the installation. 

Содержание DVC55SPPXLP-1

Страница 1: ...combustion which can cause death or serious illness Installer Leave this manual with the appliance Consumer Retain this manual for future reference WARNING If the information in these instructions ar...

Страница 2: ...duction 6 Specifications 6 Gas Supply 7 8 Clearances 8 Installation Instructions 9 11 Lighting Instructions 12 Pilot Flame Characteristics 13 Main Burner Flame Characteristics 13 Wiring 14 Service and...

Страница 3: ...The appliance should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required due to excessive lint from carpet ing bedding materials etc It i...

Страница 4: ...gas can adsorb or absorb onto or into walls masonry and other materials and fabrics in a room That will take some of the odorant out of the gas reducing its odor intensity LP Gas may stratify in a clo...

Страница 5: ...oxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE A metal or plastic identification plate shall be pe...

Страница 6: ...ied Installing Agency Installation and replacement of gas piping gas utilization equip ment or accessories and repair and servicing of equipment shall be performed only by a qualified agency The term...

Страница 7: ...local authorized installer for installation or relocation Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases The gas lines must be checked f...

Страница 8: ...distance from the center of the vent cap to the nearest outside corner or obstruction is 24 inches CLEARANCES Checking Manifold Pressure Both Propane and Natural gas valves have a built in pressure re...

Страница 9: ...provided Side outlet kit 10 boot assembly with register SOK 1 for warm air discharge into an adjoining room may be installed on either side of the furnace at the required clearance of 4 inches to adj...

Страница 10: ...ove old furnace cement from both ends of 4 diameter flue outlet tube 3 Attach 6 diameter air inlet tube onto the collar of air drop assembly Attach caulked outside mounting plate into the 6 diameter a...

Страница 11: ...e projection 2 x 4 framing whose outside dimensions match the overall dimensions of the mounting plate is recommended The 2 x 4 framing protects siding from possible warpage or discoloration All joint...

Страница 12: ...power to the appliance FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of l...

Страница 13: ...emovingthe burner door from the combustion chamber remove rear burner pilot burner and front burner With front and rear burners removed from furnace force water into the ribbon ports and dry with air...

Страница 14: ...toggle switch or thermostat remove the wire nut from the two wires from the valve Run additional wire from the valve wires to the ON OFF device Install the ON OFF device in the same room as the furnac...

Страница 15: ...r Does Not Light Pilot With air in the gas line such as when the furnace is first installed or was off all summer the pilot flame may be too lean to ignite on the first few trials Turn the control val...

Страница 16: ...l Gas 28 DV808 Pilot Tubing 29 DV824 Front Burner 30 P8842 Main Burner Orifice Natural Gas Two Required 30 P8853 Main Burner Orifice LP Gas Two Required 31 DV687 Manifold and Plate Assembly 32 M148 Ma...

Страница 17: ...Page 17 32188 0 0616 PARTS VIEW...

Страница 18: ...ranty parts All parts listed in the Parts List have a Part Number When ordering parts first obtain the Model Number and Serial Number from the name plate on your equipment Then determine the Part Numb...

Страница 19: ...le cancelled check or payment record should be kept to verify purchase date and establish warranty period Ready access to the appliance for service What Is Not Covered Damages that might result from t...

Страница 20: ...mfort Systems Empire Comfort Systems Inc Belleville IL If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question please cont...

Страница 21: ...rieuses maladies Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables dans le voisnage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE...

Страница 22: ...st chaud lorsque le radiateur est en fonction L installation et la r paration doivent tre faites par une per sonne qualifi e L appareil doit tre inspect avant l usage et au moins une fois par ann e pa...

Страница 23: ...bas Attendez que les pompiers vous assurent de la s ret de ces endroits avant d y aller Utiliser le t l phone de votre voisin et appeler les pompiers et une personne entra n e avec le propane Ne pas...

Страница 24: ...e gaz d entrer par le capuchon de l vent Emplacement de l Ouverture dans le Mur Le radiateur doit tre situ sur un mur ext rieur Trouver les montants du mur ainsi l ouverture dans le mur sera entre les...

Страница 25: ...d espace libre aux mat riaux combus tibles venant du d gage ment du registre de chaque c t Entr e de gaz Enlever plinthe et moulure ouverture d vent 7 1 2 19cm Mur ar ri re Minimum d espace libre au c...

Страница 26: ...l entr e de la pluie Attacher la plaque ext rieure de montage au mur ext rieur avec 4 vis 10 x 1 38mm Les vis sont fournies 4 Appliquer du ciment pour radiateur au collet de la sortie Emplacement de l...

Страница 27: ...ourrev tementnedoitpasexc derune paisseur totale de 13 33 02cm pour le DV 55 voir Figure 5a AVERTISSEMENT Lorsque l ensemble d vent pour le rev tementenvinyleDV 822oulaconstructionfaitede2 x 4 5 08cm...

Страница 28: ...x et de raccords en m tal ondul ANS Z21 45 Connexions flexibles d appareil autre qu en m tal Les connexions ci dessus peuvent tre utilis es si elles sont accept es par les autorit s ayant juridiction...

Страница 29: ...index no 4 pi ce no 712059 Les joints d tanch it doivent tre tir s pour s adapter sur les boulons du moteur dans les espaces pour joint d tanch it Le moteur et les joints d tanch it peuvent tre insta...

Страница 30: ...tournerle bouton de contr le de gaz N utiliserjamais des outils Si vousnepouvezpaspousseroutournerleboutonavecvos mains n essayerpasdeler parer appeleruntechnicien qualifi Forcer ou essayer de r parer...

Страница 31: ...a veilleuse et r allumer La veilleuse s enflamme mais s teint lorsque le bouton est rel ch 1 Suivre les instructions et appuyer sur le bouton plus long temps et fermement 2 D terminer si la flamme de...

Страница 32: ...semblage du br leur avant 30 P8842 Br leur principal avec ouverture gaz naturel exige deux 30 P8853 Br leur principal avec ouverture gaz propane exige deux 31 DV687 Tuyau de gaz et assemblage de plaqu...

Страница 33: ...Page 13 32188 0 0616 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 2623...

Страница 34: ...aiement pour attester de la date d achat et tablir la p riode de garantie Acc s imm diat l appareil pour la r paration Ce qui n est pas couvert Dommages pouvant r sulter de l emploi de l emploi abusif...

Страница 35: ...Page 15 32188 0 0616 NOTES DE SERVICE...

Страница 36: ...ire Comfort Systems Inc Belleville IL Pour toute question g n rale concernant nos produits veuillez nous envoyer un courriel info empirecomfort com Pour toute question d entretien ou de r paration veu...

Отзывы: