
39358-3-1019
Page 19
Figure 26
MINIMUM HOLE LOCATION DIMENSIONS FOR THROUGH
THE WALL HORIZONTAL INSTALLATIONS WITH 90 DEGREE
ELBOW OFF TOP OF FIREPLACE
FIRePLACe
SeRIeS
HARD eLBoW DIMeNSIoNS
"A"
"B"
"C"
DVP36FP
43-1/2"
(1105mm)
4-1/2"
(114mm)
6-1/2"
(165mm)
FIRePLACe
SeRIeS
FLeX PIPe 90 DeGRee BeND
"A"
"B"
"C"
DVP36FP
45"
(1143mm)
4-1/2"
(114mm)
6-1/2"
(165mm)
Positioning the Fireplace
Determine the exact position of the appliance so the direct vent
termination will be centered (if possible) between two studs. This
will avoid any extra framing. All vent kit pipes should be assembled
on the unit after the unit is moved into the final position.
Cutting the Hole
After the fireplace has been positioned in its permanent location,
the hole through the exterior wall of the house can be cut. This hole
must be 11" (280mm) high x 9-1/8" (232mm) wide with its center line
determined by the amount of vertical rise and horizontal run of the
termination.
See Figures 26 and 39.
When locating the hole it must
be noted that the bottom of the cap must be 12" (305mm) above the
ground level, and top of the cap must be no less than 18" (457mm)
below a combustible projection, and no closer than 9" (229mm) to
any wall running parallel to vent termination.
See Figure 27.
Figure 27
Figure 28
VeNtING FIRePLACe - toP (CoNt’D)
Содержание DVP36FP30N-5
Страница 20: ...39358 3 1019 Page 20 Figure 29 Figure 30 Figure 31 EXAMPLES TOP VENT RUN...
Страница 37: ...39358 3 1019 Page 37 Figure 57 DVVK 4FV DIRECT VENT TERMINATION KIT CONT D...
Страница 46: ...39358 3 1019 Page 46 Figure 70 MILLIVOLT SYSTEM STANDING PILOT WIRING DIAGRAM...
Страница 70: ...39358 3 1019 Page 70 PARTS VIEW...
Страница 78: ...39358 3 1019 Page 78 APPLIANCE SERVICE HISTORY Date Dealer Name Service Technician Name Service Performed Notes...