CG Drives & Automation 01-6048-01r3
Built-in functions
33
3.10.1 Modbus register list
Table 9
Input Register read access (function code 04)
Register
Starting
address
Name
Description
R/W Comment
Memory* Min
Max
Default
30002
1
Mbus Ver
Protocol
version
R
Changes when
there is a Modbus
version change
V
1
256
30003
2
HW
Hardware
version
R
**
V
1
65535
30004
3
SW
Software
version
R
**
V
1
65535
30006
5
Nrem
Total No. of
alarms for
belt failure
R
Total No. of
alarms for belt
failure
NV
0
65535 0
30007
6
Nlocked
Total No. of
alarms for
motor failure
R
Total No. of
alarms for motor
failure
NV
0
65535 0
30008
7
Nsp
Total No. of
alarms for
voltage
failure
R
Total No. of
alarms for voltage
failure
NV
0
65535 0
30010
9
M1
Motor Type
R
EMX-B version of
the motor 15, 25,
35
V
15
35
-
30011
10
n1
DIP setting
for Max
speed
R
Reads DIP value
for 16 speed
presets. 0 (100%)
to 15 (25%)
0
15
0
30013
12
n
Actual speed
motor
R
Motor speed in
RPM. +ve
clockwise & -ve
counter-
clockwise
V
-600 600
0
30015
14
Switch
Dip switch
setting
R
Reads all 10 DIP
switches
0
1024
0
* V = Volatile memory, NV =Non volatile memory
**) Decoded as “TT.XXXXXXX.YYYYYYY” (16 bits coding)
where TT is type, 0= release, 1=prerelease, 2= beta, 3= alpha
XXXXXXX is main version number
YYYYYYY is minor version number
Содержание EMX-B
Страница 1: ...Emotron EMX B Drive system for rotary heat exchangers Instruction manual English...
Страница 2: ......
Страница 8: ...4 CG Drives Automation 01 6048 01r3...
Страница 16: ...12 Description CG Drives Automation 01 6048 01r3...
Страница 56: ...52 Technical Data CG Drives Automation 01 6048 01r3...
Страница 58: ...54 Appendix CG Drives Automation 01 6048 01r3 7 2 Front label Fig 17 Front label...
Страница 59: ......