CG Drives & Automation 01-6048-01r3
Built-in functions
37
40026
25
Comp
E17
Compensation,
17 (85% signal)
[%*10]
R/W
Compensation, 17
(85% signal)
[%*10]
NV
0
1000
497
40027
26
Comp
E18
Compensation,
18 (90% signal)
[%*10]
R/W
Compensation, 18
(90% signal)
[%*10]
NV
0
1000
620
40028
27
Comp
E19
Compensation,
19 (95% signal)
[%*10]
R/W
Compensation, 19
(95% signal)
[%*10]
NV
0
1000
800
40029
28
Comp
E20
Compensation,
20 (100%
signal) [%*10]
R/W
Compensation, 20
(100% signal)
[%*10]
NV
0
1000
1000
40031
30
Test
Sets/reads unit
into test mode
R/W
0 = Not test mode
1 = Test mode
Same operation as
test switch
V
0
1
0
40034
33
Ctrl
Control signal/
PrcSet
R/W
Control signal via
MODBUS
V
0
1000
0
40035
34
Address
Address
R/W Slave ID
NV
1
256
30
40036
35
Baud
Modbus
baudrate
R
Modbus Baud
rate. Read only
Baudrate divided
by 100, ex, 96,
192, 384, 576,
1152
NV
96
192
96
40037
36
Par
Parity
R
Modbus parity
Read only
0=N
1=E
2=O
NV
0
2
0
40038
37
Stop
bits
Stop bits
R
Sets Modbus Stop
bits
0 = one stop bit
1 = two stop bits
U / NV 0
1
0
40040
39
Defrost
Enable/Disable
Defrost mode
R/W
0 = Normal
operation
1= Defrosting
V
0
1
0
Table 10
Holding Register read/write access (function code 03, 06)
Register
Starting
address
Name
Description
R/W
Comment
Memory* Min Max
Default
Содержание EMX-B
Страница 1: ...Emotron EMX B Drive system for rotary heat exchangers Instruction manual English...
Страница 2: ......
Страница 8: ...4 CG Drives Automation 01 6048 01r3...
Страница 16: ...12 Description CG Drives Automation 01 6048 01r3...
Страница 56: ...52 Technical Data CG Drives Automation 01 6048 01r3...
Страница 58: ...54 Appendix CG Drives Automation 01 6048 01r3 7 2 Front label Fig 17 Front label...
Страница 59: ......