38
Built-in functions
CG Drives & Automation 01-6048-01r3
*
V = Volatile memory
NV =Non volatile memory
40046
45
Motor
Test
speed
Put in the test
speed request
in rpm (motor)
Note: Only for
testing motor
R/W
Default is 0 i.e.
Motor is in normal
operation. When
written into the
register, all the
other functions are
disabled and
motor will run at
the specified
speed.
V
0
500
0
40047
46
Min
speed
Minimum
speed (rpm)
R/W
Minimum value of
the speed
NV
4
500
4
40048
47
Cool
heat
mode
Cooling or
heating mode
R/W
0 = Cooling mode
1= Heating mode
V
0
1
0
40049
48
Max
heat
Maximum
speed in
heating mode
(rpm)
R/W
Maximum speed of
the motor is
decided here when
in heating mode.
Only active when
DIP 1-4 are all Off
and when modbus
enabled.
NV
0
Dep.
on DIP
1-4
setting
500
40050
49
Max
cool
Maximum
speed in
cooling mode
(rpm)
R/W
Maximum speed of
the motor is
decided here when
in cooling mode.
Only active when
DIP 1-4 are all Off
and when modbus
enabled.
NV
0
Dep.
on DIP
1-4
setting
500
40051
50
Force
Stop
Stop motor
R/W
0 = go back to
normal
operation
1= Force Motor to
stop.
V
0
1
0
Table 10
Holding Register read/write access (function code 03, 06)
Register
Starting
address
Name
Description
R/W
Comment
Memory* Min Max
Default
Содержание EMX-B
Страница 1: ...Emotron EMX B Drive system for rotary heat exchangers Instruction manual English...
Страница 2: ......
Страница 8: ...4 CG Drives Automation 01 6048 01r3...
Страница 16: ...12 Description CG Drives Automation 01 6048 01r3...
Страница 56: ...52 Technical Data CG Drives Automation 01 6048 01r3...
Страница 58: ...54 Appendix CG Drives Automation 01 6048 01r3 7 2 Front label Fig 17 Front label...
Страница 59: ......