86
1. DESCRIZIONE DEI COMPONENTI
GB
GB
7. LIST OF PARAMETERS "SMART MT"
7. LIST OF PARAMETERS "SMART MT"
Menù
label
Par
Label
Description
U.m.
Range
Default
C-TH
PW
Address
(Base 0)
min
max
EHS
137
How to activate heat generators:
0: Additional generator disabled
1: When the additional generator is activated, the heat pump switches
off.
2: When the supplementary generator is activated, the heat pump re-
mains on.
-
0
2
0
S
16408
138
Bivalence set point (additional generator):
Outdoor temperature at which the free contact "Ext. Heat Source ”
can be activated (clamps F-L)
°C
-15.0
10.0
5.0
S
16409
139
Bivalence delay (additional generator):
On-going time, in which the outdoor temperature is below than the
bivalence set point, until the free contact “Ext. Heat Source ” activates
(clamps F-L)
h:
min
00:01
02:00
00:30
S
16410
PUMP
140
Factory parameter, do not change
-
-
-
0
S
16487
AL
Room temperature probe fault CRONO-TH
9007
Ambient humidity probe fault CRONO-TH
9008
Outdoor temperature probe fault
9003
Outlet water temperature probe fault
9005
Error signal “Temp. Water Supply System” (clamps 3-4)
9004
Sanitary storage temperature probe fault
9006
Heat pump error. Error code on PCB display
9010
Remote controller connection error
9009
Condensation risk for the radiant cooling system
9012
Overheating risk for the radiant heating system
9013
Содержание EH0618DC
Страница 106: ...106 Note...
Страница 107: ...107 Note...