
41
Min
Min
Default
Default
Unit
Unit
Max
Max
0
0
1
1
0
0
129
129
0
0
12
12
The same as Configurable Output-1 options
The same as Configurable Output-1 options
CONF. EXP. OUTPUT-7 (
)
Outputs->Conf. exp. output-7
CONF. EXP. OUTPUT-8 (
)
Outputs->Conf. exp. output-8
Polarity
Polarity
Function
Function
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
0- Normally Open (Close To Activate)
1- Normally Close (Open To Activate)
CONFIGURABLE OUTPUTS SELECTIONS
Output is not used
The output indicates that the internal sounder is operating. It may be use for external sounder.
This output indicates that a digital input that has been configured as 'auto start inhibit' is active.
This output indicates that a digital input that has been configured as 'Auxiliary Source 1 failure' is active.
This output indicates that a battery high voltage alarm has occurred.
This output indicates that a battery low voltage alarm has occurred.
This output indicates that a scheduled run(exercise) has been called for. If the unit is in the 'auto' and mains
okay, the unit will change mode to 'test' and the generator will run if no shutdown alarms are present.
This output indicates that a warning, electrical trip or shutdown alarm has been activated.
This output indicates that an electrical trip alarm has been activated. This output can only be reset by removal of
the fault and by then pressing the RESET button.
This output indicates that a shutdown alarm has been activated. This output can only be reset by removal of the
fault and by then pressing the RESET button or by using an external 'alarm reset' input.
0 NOT USED
3 AUDIBLE ALARM
4 AUTO START INHIBIT
5 AUXILIARY SOURCE 1 FAILURE
6 BATTERY HIGH VOLTAGE
7 BATTERY LOW VOLTAGE
8 CALLING FOR SCHEDULED RUN(EXERCISE)
11
12 COMMON ALARM
13 COMMON ELECTRICAL TRIP ALARM
14 COMMON SHUTDOWN ALARM
1 AIR FLAP CONTROL
2 ALARM RESET
9 AUXILIARY SOURCE 2 FAILURE
10
15 COMMON WARNING ALARM
Normally used to control an air flap, this output becomes active upon an Engine shutdown failure situation.
Inactive when the set has come to rest.
The output indicates that an alarm reset being performed. Once the alarm reset has been completed, the output
become inactive again. The output could be used to give an external reset signal to external systems.
This output indicates that a digital input that has been configured as 'Auxiliary Source 2 failure' is active.
This output indicates that a warning alarm has been activated. This output is normally self-resetting on removal
of the fault.
RESERVED
RESERVED