89
Automatic Reset
When count value reaches to SET2 value, count value is reset and
Output-2 becomes active. If Output-2 pulse time is
Then Output-2 does not change position until manual reset input is
active. If Output-2 pulse time is not 0, Output-2 becomes
inactive at the end of the pulse time.
When Output-2 becomes active, 1 is added to batch count value is
(Batch count value can be observed by pressing SET1 button). When
number of how many times Output-2 is active becomes equal to SET1
value, then Output-1 becomes active and Batch count value is reset
automatically. If Output-1 pulse time is , then
Output-1 does not change position until manual reset input is active. If
Output-1 pulse time is not 0, then Output-1 becomes inactive
at the end of the pulse time.
How it operates in BATCH COUNTER function is explained below:
Counting direction : 0
Þ
P (Upcount)
=
Reset
SET2
Count
value
Ch-A
SET1
Batch
value
Output-1
Output-1
Output-2
0
0
=
=
=
Þ