EM-GU User’s Manual
Appendix I Function Code Table
23
Code
Parameter Name
Functional description
Default
F22
Running Overcurrent(OC) P.C.
50%-600%
200%
F23
Running Overcurrent(OC) Time
0s-6000s
5s
F24
Over Voltage P.C.
100%~140%
120%
F25
Over Voltage Time
0s~120s
5s
F26
Under Voltage P.C.
50%-100%
80%
F27
Under Voltage Time
0s~120s
5s
F28
Current Unbalance P.C.
20%~100%
40%
F29
Current Unbalance Time
0s~120s
10s
F30
Under Load P.C.
10%~100%
50%
F31
Under Load Time
1s~120s
10s
F32
Phase Sequence
0: Any
1: Positive
2: Negative
0
F33
IA Calibration
10%~1000%
100%
F34
IB Calibration
10%~1000%
100%
F35
IC Calibration
10%~1000%
100%
F36
Voltage Calibration
10%~1000%
100%
F37
4-20mA Lower Calibration
0%~150.0%
20.0%
F38
4-20mA Upper Calibration
0%~150.0%
100.0%
F39
Running Over Load(OL)
0: Alarm & Stop
1: Ignore
0
F40
Starting Over Current(OC)
0: Alarm & Stop
1: Ignore
0
F41
Running Over Current(OC)
0: Alarm & Stop
1: Ignore
0
F42
Over Voltage
0: Alarm & Stop
1: Ignore
0
F43
Under Voltage
0: Alarm & Stop
1: Ignore
0
F44
Current Unbalance
0: Alarm & Stop
1: Ignore
0
F45
Under Load
0: Alarm & Stop
1: Ignore
0
F46
Over Heat
0: Alarm & Stop
1: Ignore
0
F47
Language
0:English
1:
中文
1
*F48
MB Soft Version
-
-
F49
Pump Functions
0:None
1: Float Ball
2: Electrical Pressure Gauge
3: Level relay Supply
4: Level relay Drain
0
*F50
Display Soft Version
-
-