Appendix I Function Code Table
EM-GU User’s Manual
22
Appendix I Function Code Table
Note: Parameters with "*" are read-only parameters and cannot be changed.
Code
Parameter Name
Functional description
Default
*F00
Soft Starter Rated Current
-
Model
dependent
*F01
Soft Starter Rated Voltage
-
Model
dependent
F02
Mot Rated Current
-
Model
dependent
F03
Control Mode
0: Disable
1: Keypad
2: Terminal
3: Key+Term
4: Communication
5: Key+Comm
6: Term+Comm
7: Key+Term+Comm
3
F04
Start Mode
0: Voltage Ramp
1: Current Limit
2: Torque Start
0
F05
CLS Current Limited
50%~600%
300%
F06
Initial Start Voltage
30%~80%
35%
F07
VRS Start Time
1s~120s
15s
F08
Stay Voltage
60%~85%
65%
F09
Initial Ramp Time
1s~10s
5s
F10
Stay Time
1s~120s
10s
F11
End Ramp Time
1s~10s
3s
F12
Soft Stop Time
0s~60s
0s
F13
Programmable Relay
0: Disable
1: Power on
2: Starting
3: Bypass
4: Stopping
5: Running
6: StandBy(Ready)
7: Fault
7
F14
Programmable Delay Time
0~600s
0s
F15
4-20 mA Current Limit
50%~500%
200%
F16
Motor Wiring Mode
0: Line Mode
1: Delta Mode
0
F17
Modbus Address
1~127
1
F18
Modbus Baud rate
0:2400
1:4800
2:9600
3:19200
2
F19
Running overload(OL) Class
1~30
10
F20
Starting Overcurrent(OC) P.C.
50%-600%
500%
F21
Starting Overcurrent(OC) Time
0s-120s
5s