background image

3. Operation and Display 

EM-GU User’s Manual 

 

10

 

Note: t means action time, Tp means running OL class, I means running current

Ip means motor rated 

current. 

The table of motor overload protection characteristics is as follows: 

Overload 

Class 

Overload capacity 

1.05Ie 

1.2Ie 

1.5Ie 

2Ie 

3Ie 

4Ie 

5Ie 

6Ie 

 

79.5s 

28s 

11.7s 

4.4s 

2.3s 

1.5s 

1s 

 

159s 

56s 

23.3s 

8.8s 

4.7s 

2.9s 

2s 

 

398s 

140s 

58.3s 

22s 

11.7s 

7.3s 

5s 

10 

 

795.5s 

280s 

117s 

43.8s 

23.3s 

14.6s 

10s 

20 

 

1591s 

560s 

233s 

87.5s 

46.7s 

29.2s 

20s 

30 

 

2386s 

840s 

350s 

131s 

70s 

43.8s 

30s 

Note: 

  means no action.

 

 

Motor overload protection characteristic curve diagram 

F20 

Starting Over Current(OC) P.C.

   

 

Range: 50%-600% (Default: 500%) 

Description: Set the multiple of overcurrent for soft starter starting. 

F21 

Starting Over Current(OC) Time

 

 

Range: 0s-120s (Default: 5s) 

Description: Set the overcurrent protection trigger delay time when the soft starter starting. 

F22 

Running Over Current(OC) P.C.

 

 

Range: 50%-600% (Default: 200%) 

Description: Set the multiple of overcurrent for soft starter running. 

F23 

Running Over Current(OC) Time

 

 

Range: 0s-6000s (Default: 5s) 

Description: Set the overcurrent protection trigger delay time when the soft starter running. 

F24 

Over Voltage P.C.

 

 

Range: 100%~140% (Default: 120%) 

Description: Set the multiple of overvoltage for soft starter. 

F25 

Over Voltage Time 

 

Range: 0s~120s (Default: 5s) 

Description: Set soft starter overvoltage protection trigger delay time. 

F26 

Under Voltage P.C.

 

Содержание EM-GU Series

Страница 1: ......

Страница 2: ...s to the output terminals U V W Please seal the terminal switch insulation glue after finishing connect them The soft starter and its enclosures must be fixedly earthed During the maintenance and repa...

Страница 3: ...2 6 Description of control circuit terminals 5 3 Operation and Display 6 3 1 Keypad and Operation 6 3 2 Description of Function Parameters 8 3 3 Fault Diagnosis and Solution 14 4 Test Run and Applicat...

Страница 4: ...functions for easy fault finding Multiple protection functions such as overcurrent overheat phase loss and thermal overload Humanized design detachable operation panel built in Chinese and English dis...

Страница 5: ...del and Installation Dimension Diagram 2 2 EM GU installation dimension and mounting holes Model Rated Power Rated Current External Dimensions mm Installation Dimensions mm KW A H W D H1 W1 d EM GU3 0...

Страница 6: ...h soft starters Starting Frequency Not more than 4 hour when the motor is started with full load The starting time is according to the loading equipment Cooling Mode Fan cooling Protective Grade IP20...

Страница 7: ...evices Connection Diagram EM GU series soft starters can be connected to the motor by line mode connection or delta mode connection Line Mode connection Diagram 2 4 EM GU device connection diagram Lin...

Страница 8: ...l Input and output signal terminals for MODBUS RTU protocol communication 485 Digital input IN1 24V Run When F49 0 there are two ways of connections for your selection those are 2 wire connection and...

Страница 9: ...it Cancel key Exit menu or cancel modification of parameters Shift key The fault log can be cycled through while on the main display screen and select the digit to be modified when modifying parameter...

Страница 10: ...and press MENU ENTER key again to enter the parameter that needs to be modified select the option or modify the value by UP key or DOWN key and then press MENU ENTER key again means that the new data...

Страница 11: ...ad control and communication control are valid 6 Term Comm Both terminal control and communication control are valid 7 Key Term Comm Keypad control terminal control communication control all valid F04...

Страница 12: ...Select programmable relay output method F14 Programmable Delay Time Range 0 600s Default 0s Description Set the programmable output relay closed delay time F15 4 20 mA Current Limit Range 50 500 Defau...

Страница 13: ...Starting Over Current OC P C Range 50 600 Default 500 Description Set the multiple of overcurrent for soft starter starting F21 Starting Over Current OC Time Range 0s 120s Default 5s Description Set t...

Страница 14: ...2 Default 0 Option 0 Any 1 Positive 2 Negative F33 IA Calibration Range 10 1000 Default 100 Description Calibration of the soft starter s current monitoring circuit to match the external current measu...

Страница 15: ...Over Voltage Range 0 1 Default 0 Option 0 Alarm Stop 1 Ignore The protection function is disabled F43 Under Voltage Range 0 1 Default 0 Option 0 Alarm Stop 1 Ignore The protection function is disable...

Страница 16: ...n stop 3 Level relay Supply IN1 off and IN2 off start IN1 on and IN2 on stop 4 Level relay Drain IN1 off and IN2 off stop IN1 on and IN2 on start Note When F49 0 the IN3 function is fault output When...

Страница 17: ...lty Related parameters No parameter adjustment Output phase loss 1 Check whether the SCR or thyristor is damaged 2 Motor cable has one phase or multiple phases open circuit Please check whether the mo...

Страница 18: ...he parameters Related parameters F20 F21 F40 External Fault 1 External fault terminal has input Please check external input terminal Related parameters No parameter adjustment Phase Sequence 1 The inp...

Страница 19: ...n Press key or external stop button can reset the error state Note When ambient temperature is less than 10oC the starter should be power on to preheat for 30 minutes and then to start 5 2 Special App...

Страница 20: ...duction equipment Intelligent motor soft starter the application of network technology used motor control technology to adapt to the rapid development of electric power automation technology in the hi...

Страница 21: ...045 45 90 EM GU3I 055 55 110 EM GU3I 075 75 150 EM GU3I 090 90 180 350 950 400 EM GU3I 115 115 230 EM GU3I 132 132 260 400 1130 400 EM GU3I 160 160 320 EM GU3I 200 200 400 EM GU3I 250 250 500 600 135...

Страница 22: ...en soft stop Parameters setting The parameter settings are consistent with the online soft starter parameters please refer to chapter 3 2 Note The main power circuit breaker must be closed before the...

Страница 23: ...code 01 Code 03 06 Function description Read register Write in one register 03 WORD 6 2 2 Address Definition Addresses corresponding to parameters Parameter Code Address F00 F50 0x0000 0x0032 Control...

Страница 24: ...n 0 Off Bit0 IN1 Start Bit1 IN2 Stop Bit2 IN3 Fault 6 3 Abnormal Feedback Code Name Explanation 01 Illegal function Soft starter does not support this function code 02 Illegal data address Illegal add...

Страница 25: ...2 Torque Start 0 F05 CLS Current Limited 50 600 300 F06 Initial Start Voltage 30 80 35 F07 VRS Start Time 1s 120s 15s F08 Stay Voltage 60 85 65 F09 Initial Ramp Time 1s 10s 5s F10 Stay Time 1s 120s 10...

Страница 26: ...00 100 F34 IB Calibration 10 1000 100 F35 IC Calibration 10 1000 100 F36 Voltage Calibration 10 1000 100 F37 4 20mA Lower Calibration 0 150 0 20 0 F38 4 20mA Upper Calibration 0 150 0 100 0 F39 Runnin...

Страница 27: ......

Отзывы: