EM-GU User’s Manual
3. Operation and Display
9
Description: Set F08 hold time, valid for torque starting.
F11
End Ramp Time
Range: 1s~10s (Default: 3s)
Description: Set end acceleration time, valid for torque starting.
F12
Soft Stop Time
Range: 0s~60s (Default: 0s)
Description: Set the time required to soft stop the motor, if the value is “0”, the motor will free stop.
Note: One soft starter for 2 motor, this code should set "0".
F13
Programmable Relay
Range: 0~7 (Default: 7)
Option: 0: Disable
1: Power on
2: Starting
3: Bypass
4: Stopping
5: Running
6: StandBy(Ready)
7: Fault
Select programmable relay output method.
F14
Programmable Delay Time
Range: 0~600s (Default: 0s)
Description: Set the programmable output relay closed delay time.
F15
4-20 mA Current Limit
Range: 50%~500% (Default: 200%)
Description: Set analog current upper limit.
F16
Motor Wiring Mode
Range: 0~1 (Default: 0)
Option: 0: Line Mode
1: Delta Mode
Select motor wiring mode.
F17
Modbus Address
Range: 1~127 (Default: 1)
Description: Set soft starter communication address.
F18
Modbus Baud rate
Range: 0~3 (Default: 2)
Option: 0:2400
1:4800
2:9600
3:19200
F19
Running Over Load(OL) Class
Range: 1~30 (Default: 10)
Description: Set different levels of overload protection
。
The overload protection adopts anti-time protection control, and the formula as below:
Protection time t =
35 ∗ Tp
(I/Ip)2 − 1