Unidrive M702 User Guide
97
Issue Number: 3
00.042
Number Of Motor Poles
{05.011}
Automatic (0) to 480 Poles (240)
Automatic (0)
6 Poles (3)
RW Num
US
00.043
Rated Power Factor
{05.010}
0.000 to 1.000
0.850
RW Num
RA
US
Position Feedback Phase Angle
{03.025}
0.0 to
359.9 °
RW Num ND
US
00.044
Rated Voltage
{05.009}
±VM_AC_VOLTAGE_SET
200V drive: 230V
50Hz default 400V drive: 400V
60Hz default 400V drive: 460V
575V drive: 575V
690V drive: 690V
RW Num
RA
US
00.045
Rated Speed
{05.008}
0 to
180000 rpm
0.00 to
50000.00
rpm
50Hz default:
1500 rpm
60Hz default:
1800rpm
50Hz default:
1450 rpm
60Hz default:
1750rpm
RW Num
US
Motor Thermal Time Constant 1
{04.015}
1.0 to
3000.0 s
89.0 s
RW Num
US
00.046
Rated Current
{05.007}
±VM_RATED_CURRENT
Maximum Heavy Duty Rating (11.032)
RW Num
RA
US
00.047
Rated Frequency
{05.006}
0.0 to
3000.0 Hz
0.0 to
1667.0 Hz
50Hz default: 50.0 Hz
60Hz default: 60.0 Hz
RW Num
US
00.048
Drive Mode
{11.031}
Open-loop (1), RFC-A (2), RFC-S (3), Regen (4)
Open-loop (1)
RFC-A (2)
RFC-S (3)
RW
Txt
ND NC PT
00.049
User Security Status
{11.044}
Menu 0 (0), All Menus (1), Read-only Menu 0 (2),
Read-only (3), Status Only (4), No Access (5)
Menu 0 (0)
RW
Txt
ND
PT
00.050
Software Version
{11.029}
0 to 99999999
RO Num ND NC PT
00.051
Action On Trip Detection
{10.037}
0 to 31
0
RW
Bin
US
Parameter
Range
Default
Type
OL
RFC-A
RFC-S
OL
RFC-A
RFC-S
RW
Read / Write
RO
Read only
Num
Number parameter
Bit
Bit parameter
Txt
Text string
Bin
Binary parameter
FI
Filtered
ND
No default value
NC
Not copied
PT
Protected parameter
RA
Rating dependent
US
User save
PS
Power-down save
DE
Destination
IP
IP address
Mac
Mac address
Date
Date parameter
Time
Time parameter
Содержание Unidrive M702
Страница 283: ......
Страница 284: ...0478 0002 03 ...