100
Unidrive M702 User Guide
Issue Number: 3
6.2 Parameter descriptions
6.2.1 Pr mm.000
Pr
mm.000
is available in all menus, commonly used functions are provided as text strings in Pr
mm.000
shown in Table 6-1. The functions in Table
6-1 can also be selected by entering the appropriate numeric values (as shown in Table 6-2) in Pr
mm.000
. For example, enter 7001 in Pr
mm.000
to
erase the file in NV media card location 001.
Table 6-1 Commonly used functions in xx.000
Value
Equivalent value
String
Action
0
0
[No Action]
1000
1
[Save parameters]
Save parameters when under voltage is not active and low voltage threshold is not active
6001
2
[Load file 1]
Load the drive parameters or user program file from NV media card file 001
4001
3
[Save to file 1]
Transfer the drive parameters to parameter file 001
6002
4
[Load file 2]
Load the drive parameters or user program file from NV media card file 002
4002
5
[Save to file 2]
Transfer the drive parameters to parameter file 002
6003
6
[Load file 3]
Load the drive parameters or user program file from NV media card file 003
4003
7
[Save to file 3]
Transfer the drive parameters to parameter file 003
12000
8
[Show non-default]
Displays parameters that are different from defaults
12001
9
[Destinations]
Displays parameters that are set
1233
10
[Reset 50Hz Defs]
Load parameters with standard (50 Hz) defaults
1244
11
[Reset 60Hz Defs]
Load parameters with US (60 Hz) defaults
1070
12
[Reset modules]
Reset all option modules
11001
13
[Read Enc. NP P1]
Transfer electronic nameplate motor parameters to the drive from the P1 encoder
11051
14
[Read Enc. NP P2]
Transfer electronic nameplate motor parameters to the drive from the P2 encoder
Содержание Unidrive M702
Страница 283: ......
Страница 284: ...0478 0002 03 ...