268
Unidrive M702 User Guide
Issue Number: 3
Slot4 Error
Ethernet interface in slot 4 has detected a fault
252
The
Slot4 Error
trip indicates that the Ethernet interface in slot 4 on the drive has detected an error. The reason for the trip
can be identified by the sub-trip number.
Recommended actions:
•
Identify the reason for the trip from the trip string or from sub-trip number and resolve the error.
•
Reset the trip, If the trip persists, Hardware fault - Contact the supplier of the drive.
Trip
Diagnosis
Sub-trip
Trip string
Description
100
Link Loss
Network link has been lost
101
E/IP Timeout
An EtherNet/IP RPI timeout trip has occurred
102
E/IP Read Param
Invalid read consistency parameter
103
E/IP Write Param
Invalid write consistency parameter
104
E/IP Fault
An unexpected EtherNet/IP error has occurred
105
Modbus Timeout
The Modbus connection has timed out
106
DA-RT Timeout
DA-RX Rx link has timeout
107
DA-RT Rx Late
Rx data was received late
108
INIT Switch
109
INIT PTP
110
INIT DA-RT
111
INIT Modbus
112
INIT SMTP
113
INIT EtherNet/IP
114
INIT TCP/IP
115
Ethernet Failure
200
Software Fault
Software Fault
201
BG Overrun
Background task overrun
202
Firmware Invalid
Firmware is not compatible for the hardware version
203
Drive Unknown
Unknown drive type
204
Drive Unsupported
Unsupported drive type
205
Mode Unknown
Unknown drive mode
206
Mode Unsupported
Unsupported drive mode
207
FLASH Error
Corrupted Non-volatile FLASH
208
Database Init
Database initialization error
209
File System Init
File system initialization error
210
Mem Allocation
Memory allocation error
211
Filesystem Error
File system error
212
Config Save
Configuration file save error
213
Over Temperature
Option module over temperature
214
Drive Timeout
The drive has not responded within watchdog period
215
eCMP Comms Error
eCMP communication failure
216
TO eCMP Slot1
eCMP communication to slot 1 timeout
217
TO eCMP Slot2
eCMP communication to slot 2 timeout
218
TO eCMP Slot3
eCMP communication to slot 3 timeout
219
TO eCMP Slot4
eCMP communication to slot 4 timeout
220
I/O Overload
Digital output current demand too high
221
Factory Settings
Missing factory settings
222
Functional Test
Functional test failure
223
Config Restore
Configuration file restore error
224
Self Test Error
Power on self test error
225
Runtime Config
Runtime configuration error
Содержание Unidrive M702
Страница 283: ......
Страница 284: ...0478 0002 03 ...