Unidrive M / HS Frame 7 to 10 Power Installation Guide
89
Issue Number: 5
S
P
M
E
Te
UL
li
Table 5-3 575 V drive ratings (500 V to 575 V ±10 %)
Table 5-4 690 V drive ratings (500 V to 690 V ±10 %)
Model
Normal Duty
Heavy Duty
Max
cont
output
current
Nominal
power at
575 V
Motor
power at
575 V
Peak
current
Max
cont
output
current
Open
loop
peak
current
RFC
peak
current
Nominal
power at
575 V
Motor
power at
575 V
A
kW
hp
A
A
A
A
kW
hp
07500440
53
45
50
58.3
44
66
88
30
40
07500550
73
55
60
80.3
55
82.5
110
37
50
08500630
86
75
75
94.6
63
94.5
126
45
60
08500860
108
90
100
118.8
86
129
172
55
75
09501040
125
110
125
137.5
104
156
182
75
100
09501310
150
110
150
165
131
196.5
229.25
90
125
10501520
200
130
200
220
152
228
266
110
150
10501900
200
150
200
220
190
285
332.5
132
200
Model
Normal Duty
Heavy Duty
Max
cont
output
current
Nominal
power at
690 V
Motor
power at
690 V
Peak
current
Max
cont
output
current
Open
loop
peak
current
RFC
peak
current
Nominal
power at
690 V
Motor
power at
690 V
A
kW
hp
A
A
A
A
kW
hp
07600190
23
18.5
25
25.3
19
28.5
38
15
20
07600240
30
22
30
33
24
36
48
18.5
25
07600290
36
30
40
39.6
29
43.5
58
22
30
07600380
46
37
50
50.6
38
57
76
30
40
07600440
52
45
60
57.2
44
66
88
37
50
07600540
73
55
75
80.3
54
81
108
45
60
08600630
86
75
100
94.6
63
94.5
126
55
75
08600860
108
90
125
118.8
86
129
172
75
100
09601040
125
110
150
137.5
104
156
182
90
125
09601310
155
132
175
170.5
131
196.5
229.25
110
150
10601500
172
160
200
189.2
150
225
262.5
132
175
10601780
197
185
250
216.7
178
267
311.5
160
200
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 89 Tuesday, May 24, 2016 11:52 AM