Unidrive M / HS Frame 7 to 10 Power Installation Guide
109
Issue Number: 5
S
P
M
E
Te
UL
li
5.1.23
Terminal size and torque settings
Table 5-25 Drive control terminal data
Table 5-26 Drive relay terminal data
Table 5-27 Terminal block maximimum cable sizes
Table 5-28 Maximum crimp/lug sizes for frame size 8 to 10
Table 5-29 Drive power terminal data
Model
Connection type
Torque setting
M200 to M400
Screw terminals
0.2 N m (0.15 lb ft)
M600 to M702
Plug-in terminal block
0.5 N m (0.4 lb ft)
Model
Connection type
Torque setting
M200 to M400
Screw terminals
0.5 N m (0.4 lb ft)
M600 to M702
Plug-in terminal block
Model
Size
Terminal block description
Maximum cable size
All
All
Control connector
1.5 mm
2
(16 AWG)
All
All
2 way relay connector
2.5 mm
2
(14 AWG)
M300 to M400
7 to 9
STO connector
M600 to M702
All
2 way low voltage power 24V supply
connector
1.5 mm
2
(16 AWG)
Terminals
Maximum standard crimp (mm
2
)
Maximum standard US lug
(kcmil)
AC supply connections
2 x 185
2 x 500
AC supply ground
2 x 120
1 x 350
Motor connections
2 x 150
2 x 350
Drive output ground
2 x 150
1 x 350
Brake connection
2 x 150
2 x 350
Model
size
AC and motor terminals
DC and braking
Ground terminal
Recommended
Maximum
Recommended
Maximum
Recommended
Maximum
7
M8 Nut (13 mm AF)
M8 Nut (13 mm AF)
M8 Nut (13 mm AF)
12 N m
(8.85 lb ft)
14 N m
(10 lb ft)
12 N m
(8.85 lb ft)
14 N m
(10 lb ft)
12 N m
(8.85 lb ft)
14 N m
(10 lb ft)
8 to 10
M10 Nut (17 mm AF)
M10 Nut (17 mm AF)
M10 Nut (17 mm AF)
15 N m
(11.1 Ib ft)
20 N m
(14.8 Ib ft)
15 N m
(11.1 Ib ft)
20 N m
(14.8 Ib ft)
15 N m
(11.1 Ib ft)
20 N m
(14.8 Ib ft)
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 109 Tuesday, May 24, 2016 11:52 AM