Unidrive M / HS Frame 7 to 10 Power Installation Guide
105
Issue Number: 5
S
P
M
E
Te
UL
li
Table 5-19 Cable ratings (200 V)
Table 5-20 Cable ratings (400 V)
The nominal cable sizes below are only a guide. The mounting and grouping of cables
affects their current-carrying capacity, in some cases smaller cables may be acceptable
but in other cases a larger cable is required to avoid excessive temperature or voltage
drop. Refer to local wiring regulations for the correct size of cables.
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG or Kcmil
Input
Output
Input
Output
Nominal Max
Install
method
Nominal Max
Install
method
Nominal Max
Nominal Max
07200610
35
70
B2
35
70
B2
2
1/0
2
1/0
07200750
1
1
07200830
70
70
1/0
1/0
08201160
95
2 x 70
B2
95
2 x 70
B2
3/0
2 x 1
3/0
2 x 1
08201320
2 x 70
2 x 70
2 x 1
2 x 1
09201760
2 x 70
2 x 185
B1
2 x 95
2 x 150
B2
2 x 2/0
2 x 500
2 x 2/0
2 x 350
09202190
2 x 95
2 x 185
2 x 120
2 x 150
2 x 4/0
2 x 500
2 x 4/0
2 x 350
10202830
2 x 120
2 x 185
B1
2 x 120
2 x 150
C
2 x 250
2 x 500
2 x 250
2 x 350
10203000
2 x 150
2 x 185
C
2 x 120
2 x 150
2 x 300
2 x 500
2 x 250
2 x 350
Model
Cable size (IEC)
mm
2
Cable size (UL)
AWG or Kcmil
Input
Output
Input
Output
Nominal Max
Install
method
Nominal Max
Install
method
Nominal Max
Nominal Max
07400660
35
70
B2
35
70
B2
1
1/0
1
1/0
07400770
50
50
2
2
07401000
70
70
1/0
1/0
08401340
2 x 50
2 x 70
B2
2 x 50
2 x 70
B2
2 x 1
2 x 1/0
2 x 1
2 x 1/0
08401570
2 x 70
2 x 70
2 x 1/0
2 x 1/0
09402000
2 x 70
2 x 185
B1
2 x 95
2 x 150
B2
2 x 3/0
2 x 500
2 x 2/0
2 x 350
09402240
2 x 95
2 x 185
2 x 120
2 x 150
2 x 4/0
2 x 500
2 x 4/0
2 x 350
10402700
2 x 120
2 x 185
C
2 x 120
2 x 150
C
2 x 300
2 x 500
2 x 250
2 x 350
10403200
2 x 150
2 x 185
2 x 150
2 x 150
2 x 350
2 x 500
2 x 300
2 x 350
CAUTION