40
Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
3.9.2 EMC filter ratings
Table 3-6 Optional external EMC filter details
* At 55
°C
(131 °F).
3.9.3
Overall EMC filter dimensions
Table 3-7 Optional external EMC filter dimensions
CT part
number
Maximum
continuous
current
Voltage
rating
IP
rating
Power dissipation
at rated current
Ground leakage
Discharge
resistors
Balanced
supply
phase-to-
phase and
phase-to-
ground
Worst
case
@ 40 °C
(104 °F)
@ 50 °C
(122 °F)
IEC UL
@ 40 °C
(104 °F)
@ 50 °C
(122 °F)
A
A
V
V
W
W
mA
mA
M
Ω
4200-1132
117
102.7*
528
480
20
50
43.7
11.7
188
1.68
4200-0672
67
58.8*
759
600
25
21.9
24.5
395
2.72
4200-1972
197
172.8*
528
480
42
36.7
18.7
210
1.68
4200-1662
114
100*
759
600
39
34.1
24.3
364
2.72
4200-3021
302
277
528
480
00
34
29.7
30
202
1.68
4200-1660
166
152
759
600
13
11.4
21
332
2.72
4200-4460
446
409
528
480
37
32.4
30
283
1.68
4200-2210
221
203
759
600
16
14.0
21
434
2.72
Part Number
Dimensions (mm)
Weight
H
W
D
mm
inch
mm
inch
mm
inch
kg
lb
4200-1132
270
10.63
90
3.54
150
5.90
6
13.2
4200-0672
270
10.63
90
3.54
150
5.90
6.2
13.7
4200-1972
300
11.81
120
4.72
170
6.69
9.6
21.2
4200-1662
300
11.81
120
4.72
170
6.69
9.4
20.7
4200-3021
339
13.3
230
9.06
120
4.72
11
24.3
4200-1660
360
14.2
245
9.6
105
4.13
5.2
11.5
4200-4460
105
4.13
360
14.2
245
9.6
12
26.5
4200-2210
105
4.13
360
14.2
245
9.6
10.3
22.7
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 40 Tuesday, May 24, 2016 11:52 AM