Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
Figure 3-16 View showing sealing clamps provided in through hole mounting kit
Table 3-4 Power losses from the front of the drive when through-panel mounted
For detailed information regarding high IP through panel mounting see section
3.4.3
When designing a high IP enclosure, consideration should be given to the dissipation from
the front of the drive.
Frame size
Power loss
7
≤
204 W
8
≤
347 W
9A/9E/10E
≤
480 W