30
Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
Figure 3-11 Enclosure layout (size 9 to 10)
Ensure minimum clearances
are maintained for the drive
and external EMC filter. Forced
or convection air-flow must not
b
e restricted
b
y any o
b
ject or
ca
b
ling
Note
For EMC compliance:
1) When using an external EMC
filter, one filter is required for
each drive
2) Power ca
b
ling must
b
e at
least 100mm (4in) from the
drive in all directions
A
B
= 60 mm (2.37 in)
= 45 mm (1.77 in)
B
B
A
AC supply
contactor and
fuses or MCB
Locate as
required
Locate as
required
Enclosure
³
100mm
(4in)
³
100mm
(4in)
Signal ca
b
les
Plan for all signal ca
b
les
to
b
e routed at least
300 mm (12 in) from the
drive and any power ca
b
le
controller
External
O
ptional
b
raking
resistor and overload
Locate optional
b
raking
resistor external to
cu
b
icle (prefera
b
ly near
to or on top of the cu
b
icle).
Locate the overload
protection device as required
9
10
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 30 Tuesday, May 24, 2016 11:52 AM