4310 Wireless Position Monitor
Instruction Manual
October 2009
3
Table 1. Specifications (continued)
Power Module Limits
Standard —5 years @ 1 minute update rate with
3 additional devices communicating through it
Extended
−
Life —6 years @ 4 second rate with 3
additional devices communicating through it
Shelf life —15 years (radio off)
Update Rates
For position feedback, temperature, and power
module voltage—selectable from 4 seconds to 1
hour, 4s, 8s, 16s, 32s, 1 to 60 minutes
Factory default is 1 minute
Construction Material
Housing: Engineered resin
1. The pressure/temperature limits in this manual and any applicable standard or code limitation for valve should not be exceeded.
2. Due to the combustible nature of the lithium content, the power module has special installation, operation, storage, and/or shipping requirements. Observe all warnings included with the
power module before installing, operating, storing, or shipping. Contact your Emerson Process Management sales office if additional information is needed.
3. Contact your Emerson Process Management sales office for information on pending third party approvals.
Table 2. EMC Summary Results—Immunity
PORT
PHENOMENON
BASIC
STANDARD
TEST LEVEL
PERFORMANCE
CRITERIA
(1)
Enclosure
Electrostatic discharge (ESD)
IEC 61000-4-2
6 kV contact
8 kV air
B
Radiated EM field
IEC 61000-4-3
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
1400 to 2000 MHz @ 10V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 3V/m with 1 kHz AM at 80%
A
Rated power frequency
magnetic field
IEC 61000-4-8
30 A/m at 50 Hz & 60 Hz
100 A/m @ 50 Hz
A
Performance criteria: +/
−
2% of effect
1. A = No degradation during testing. B = Temporary degradation during testing, but is self-recovering.
Table 3. EMC Summary Results—Emissions
PORT
FREQUENCY
RANGE (MHz)
BASIC
STANDARD
EMISSIONS LEVEL
GIVEN
RATING
Enclosure
30 to 230
EN 55011
Group 1 Class A: 40 dB (uV/m) measured at 10 m distance
Group 1 Class B: 30 dB (uV/m) measured at 10 m distance
Class A & B
230 to 1000
Group 1 Class A: 47 dB (uV/m) measured at 10 m distance
Group 1 Class B: 37 dB (uV/m) measured at 10 m distance
Class A & B
1000 to 3000
Group 1 Class B
50 dB (uV/m) measured at 3 m distance, peak limit not to exceed 70 dB (uV/m)
Class A &B
3000 to 6000
Group 1 Class B
54 dB (uV/m) measured at 3 m distance, peak limit not to exceed 74 db (uV/m)
Class A & B
NOTES:
The 4310 is considered as a Group 1 device.
Industrial, Scientific, and Medial (ISM) radio frequency (RF) equipment is rated according to its Group and Class as follows;
Group I
−
Equipment in which there is intentionally generated and/or used conductively coupled radio
−
frequency energy which is necessary for the internal functioning of the equipment
itself.
Group II
−
Equipment in which radio
−
frequency energy is intentionally generated and/or used in the form of electromagnetic radiation for the treatment of material, and EDM and arc
welding equipment.
Class A
−
Equipment suitable for use in industrial and commercial environments
Class B
−
Equipment suitable for use in domestic environments