4310 Wireless Position Monitor
Instruction Manual
October 2009
18
CHANGE
UPDATE
PERIOD
WIRELESS TAB
CONFIGURE
MANUAL
SETUP
Figure 18. Change Update Rate in AMS Wireless Configurator
and AMS Device Manager
Accessing Features
Update Rate
The 4310 is shipped with a default update rate of 60
seconds. To change this either use the Field
Communicator, AMS Wireless Configurator, or AMS
Device Manager.
Field Communicator
Select Online, Configure, Manual Setup, Burst
Mode, then Update Period to verify or make changes
to the update rate. Refer to the Configure menu tree
shown in figure 16.
AMS Wireless Configurator or AMS Device
Manager
Go to Configure, Manual Setup, then select Change
Update Period from the Wireless tab to makes
changes to the update rate. See figure 18.
Trigger Points and Deadband
The 4310 is shipped with a factory default setting of
10% for the open trigger point and 90% for the
closed trigger point. The deadband is set at 5%.
Field Communicator
Select Online, Configure, Manual Setup, then
Trigger Points to verify or make changes to the
trigger point settings. Refer to the Configure menu
tree shown in figure 16.
TRIGGER POINTS TAB
CONFIGURE
MANUAL
SETUP
CHANGE
TRIGGER PTS
Figure 19. Setting Trigger Point in AMS Wireless Configurator
and AMS Device Manager
AMS Wireless Configurator or AMS Device
Manager
Go to Configure, Manual Setup, then select Change
Trigger Pts from the Trigger Points tab to make
changes to the trigger point settings. See figure 19.
Diagnostics
The 4310 includes two diagnostic features, cycle
counter and power status.
D
Cycle counter is shipped from factory with a
high value, which, in effect, disables the alert. This
alert is used with valves that have service
recommendations based on number of actuation
cycles.
Field Communicator
Select Online, Configure, Alert Setup, Cycle Count
Alert, then Alert Trigger to verify or make changes to
the cycle counter settings. Refer to the Configure
menu tree shown in figure 16.
To clear accumulated cycle value select Reset Cycle
Counter.
AMS Wireless Configurator or AMS Device
Manager
Go to Configure, Alert Setup. Enter the Alert Trigger
value on the Cycle Counter tab to set the cycle
counter. When the value turns yellow (indicating that
a change has been made) select Apply. Refer to
figure 20.