background image

4310 Wireless Position Monitor

Instruction Manual

October 2009

18

CHANGE
UPDATE
PERIOD

WIRELESS TAB

CONFIGURE

MANUAL
SETUP

Figure 18. Change Update Rate in AMS Wireless Configurator

and AMS Device Manager

Accessing Features

Update Rate

The 4310 is shipped with a default update rate of 60
seconds. To change this either use the Field
Communicator, AMS Wireless Configurator, or AMS
Device Manager.

Field Communicator

Select Online, Configure, Manual Setup, Burst
Mode, 
then Update Period to verify or make changes
to the update rate. Refer to the Configure menu tree
shown in figure 16.

AMS Wireless Configurator or AMS Device
Manager

Go to ConfigureManual Setup, then select Change
Update Period
 from the Wireless tab to makes
changes to the update rate. See figure 18.

Trigger Points and Deadband

The 4310 is shipped with a factory default setting of
10% for the open trigger point and 90% for the
closed trigger point. The deadband is set at 5%.

Field Communicator

Select Online, Configure, Manual Setup, then
Trigger Points to verify or make changes to the
trigger point settings. Refer to the Configure menu
tree shown in figure 16.

TRIGGER POINTS TAB

CONFIGURE

MANUAL
SETUP

CHANGE
TRIGGER PTS

Figure 19. Setting Trigger Point in AMS Wireless Configurator

and AMS Device Manager

AMS Wireless Configurator or AMS Device
Manager

Go to ConfigureManual Setup, then select Change
Trigger Pts
 from the Trigger Points tab to make
changes to the trigger point settings. See figure 19.

Diagnostics

The 4310 includes two diagnostic features, cycle
counter and power status.

D

Cycle counter is shipped from factory with a

high value, which, in effect, disables the alert. This
alert is used with valves that have service
recommendations based on number of actuation
cycles.

Field Communicator

Select Online, Configure, Alert Setup, Cycle Count
Alert, 
then Alert Trigger to verify or make changes to
the cycle counter settings. Refer to the Configure
menu tree shown in figure 16.

To clear accumulated cycle value select Reset Cycle
Counter
.

AMS Wireless Configurator or AMS Device
Manager

Go to ConfigureAlert Setup. Enter the Alert Trigger
value on the Cycle Counter tab to set the cycle
counter. When the value turns yellow (indicating that
a change has been made) select Apply. Refer to
figure 20.

Содержание TopWorx 4310

Страница 1: ...netic Feedback Assembly 21 Replacing the Power Module 21 Removal 22 Installation 22 Parts 23 Replaceable Parts 23 W9633 Figure 1 TopWorx 4310 Position Monitor Introduction Scope of Manual This instruction manual includes specifications installation initial setup configuration operation troubleshooting and maintenance information for the TopWorx 4310 wireless position monitor This manual describes ...

Страница 2: ...oltage Output Communication Signal 2 4 GHz DSSS WirelessHART Maximum 10 dBm EIRP at 2 46 GHz 10 mW EIRP at 2 46 GHz Wireless Classifications Class A digital device complies with part 15 of the FCC Rules Contains FCC ID LWZRM2510 Contains IC 2731A RM2510 Electromagnetic Compatibility Meets EN 61326 1 First Edition Immunity Industrial locations per Table 2 of the EN 61326 1 standard Performance is s...

Страница 3: ...V m with 1 kHz AM at 80 2000 to 2700 MHz 3V m with 1 kHz AM at 80 A Rated power frequency magnetic field IEC 61000 4 8 30 A m at 50 Hz 60 Hz 100 A m 50 Hz A Performance criteria 2 of effect 1 A No degradation during testing B Temporary degradation during testing but is self recovering Table 3 EMC Summary Results Emissions PORT FREQUENCY RANGE MHz BASIC STANDARD EMISSIONS LEVEL GIVEN RATING Enclosu...

Страница 4: ...on against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user ...

Страница 5: ... the cover of the 4310 and attach the HART modem leads to the HART terminals see figure 22 4 In AMS select the device that is connected to the HART modem Select Online Overview then Join Device to Network see figure 2 5 Remove the leads from the 4310 and close the cover 6 Install the 4310 on monitored equipment and or verify the 1420 gateway Installation WARNING Before mounting the 4310 wireless p...

Страница 6: ...field However as with any magnet care must be taken when handling the magnet assembly Another high powered magnet placed in close proximity less than 25 mm can cause 2 OR 4 INCH ARRAY NOTE VALID TRAVEL RANGE INDICATED BY WHITE ARROWS ROTARY 1 INCH ARRAY Figure 4 Magnet Assemblies permanent damage Potential sources of damaging equipment include but are not limited to transformers DC motors stacking...

Страница 7: ...the mounting bolts Any of the mounting holes may be used for linear actuators See figure 6 MOUNTING HOLES FOR ROTARY NAMUR M6 OPTIONAL MOUNTING HOLES NOTE ANY OF THE MOUNTING HOLES MAY BE USED FOR LINEAR ACTUATORS W9636 Figure 6 Housing and Mounting for Linear and Quarter Turn Actuators 7 Once the instrument is mounted perform the local interface calibration procedure as described on page 12 Verif...

Страница 8: ...REME ORIENTATION AT MID TRAVEL FLATS PARALLEL TO 4310 HOUSING CHANNEL ORIENTATION AT THE OTHER TRAVEL EXTREME W8836 1A W8836 1B Figure 9 Feedback Assembly Orientation 3 Attach the wireless position monitor to the mounting bracket using the 4 mounting bolts as shown in figure 7 4 Check for clearance between the magnet assembly and the positioner feedback slot 5 Once the instrument is mounted perfor...

Страница 9: ... at selectable update rates The update rates of the device have an effect on the number that the NUMBER OF CHILDREN IMPACT ON ON POWER MODULE LIFE NUMBER OF CHILDREN POWER MODULE LIFE YEARS 8 6 5 2 0 14 NOTE 60 SECOND UPDATE RATE CONSTANT TEMPERATURE OF 25_C 77_F 16 12 10 8 6 4 2 0 7 4 3 1 EXTENDED STANDARD Figure 12 Number of Children and Power Module Life 2 60 80 40 0 20 20 40 POWER MODULE LIFE ...

Страница 10: ...N When accessing the pushbuttons or terminals proper means of electrostatic discharge protection is required Failure to provide appropriate protection can cause the device to malfunction The primary function of the local user interface is for calibration However information for checking the status of the device as well as the connected equipment or valve is also available through the local user in...

Страница 11: ...g life value of the power module is an estimate The life span of the power module is affected by many operating conditions including The update or burst rate of the 4310 wireless position monitor The number of devices operating through this device to the gateway and their update or burst rates Network changes causing more or less traffic through the device for example a failure in another wireless...

Страница 12: ...d the second position is recorded MARKED Earlier calibration points can be used or discarded Applying calibration points without changing the valve position will result in the calibration attempt being unused or discarded The calibration status will be displayed SUCCESS indicates that the calibration procedure was successful SPAN HI indicates that a problem with the high end of travel or rotation ...

Страница 13: ...sition of the monitored equipment e g valve as a discrete value OPEN CLOSED or PARTIALLY OPEN Time Since Reset indicate the time in hours minutes and seconds since the last time the 4310 received a restart command Shortcuts Device Information D Manufacturer identifies the manufacturer of the instrument D Model indicates the device type D HART Universal Rev indicates the HART Universal Revision D D...

Страница 14: ...losed Alerts 2 3 Calibration 1 Calibration Status 2 Calibration Date 3 Calibrate Open Closed Alerts 1 Setup Open Closed Alerts 2 4 2 3 2 Figure 16 Field Communicator Menu Tree Configure Calibrate Follow the prompts on the Field Communicator to calibrate the instrument Join Device to Network allows you to enter the Network ID up to 5 digits and the Join Key 4 sets of 8 hexadecimal digits The Join K...

Страница 15: ... shipped with default values and must be changed prior to use Network ID displays the default Network ID Join Key to Network enter the Network ID up to 5 digits and the Join Key 4 sets of 8 hexadecimal digits The Join Key is used for encrypting the data on the wireless network The Network ID and the Join Key must be the same for all devices connected to a gateway D Burst Mode Burst Mode enabling b...

Страница 16: ...Closed Trigger Point indicates the set Closed Trigger Point Deadband 5 select the desired deadband Change Trigger Points select the desired Trigger Points This sets the Open Trigger Point and the Closed Trigger Point Alert Setup D Cycle Count Alert Alert Trigger select the Alert Trigger Accumulated Cycles indicates the number of accumulated cycles Reset Cycle Counter select Yes to reset the cycle ...

Страница 17: ...he status of the power module voltage D Accumulated Cycles indicates the number of accumulated cycles D Time Since Reset indicates the time in hours minutes and seconds since the last time the 4310 was restarted Run Time Extremes D Max Recorded Temp indicates the maximum recorded temperature of the 4310 D Date of Max Temp indicates when the maximum temperature was recorded D Min Recorded Temp indi...

Страница 18: ... changes to the trigger point settings Refer to the Configure menu tree shown in figure 16 TRIGGER POINTS TAB CONFIGURE MANUAL SETUP CHANGE TRIGGER PTS Figure 19 Setting Trigger Point in AMS Wireless Configurator and AMS Device Manager AMS Wireless Configurator or AMS Device Manager Go to Configure Manual Setup then select Change Trigger Pts from the Trigger Points tab to make changes to the trigg...

Страница 19: ... AMS Wireless Configurator and AMS Device Manager Principle of Operation The basic concept of the electronic positioner can be understood by visualizing a magnet mounted to a piece of equipment that either has a rotating motion or sliding linear movement The device has the ability to detect the position of the magnet and transmit wirelessly the relative position The 4310 is similar to a limit swit...

Страница 20: ...s that must be taken to protect against process media CAUTION When replacing components use only components specified by the factory Always use proper component replacement techniques as presented in this manual Improper techniques or component selection may invalidate the product specifications as indicated in table 1 Improper replacement techniques or component selection may also impair operatio...

Страница 21: ... perform the following basic steps 1 Remove the 4310 from the actuator 2 Remove the screws holding the magnet assembly to the connector arm Install the new magnet assembly per the appropriate Installation Mounting procedure Once the instrument is mounted perform the calibration routine before putting back in to service Replacing the Power Module Note The power module is designed to be field replac...

Страница 22: ...TERMINAL J1 PWR TERMINAL W9645 Figure 24 Power Module 3 Remove the 4 smaller screws providing the mechanical connection to the housing 4 Remove both power modules Installation When installing the new power modules follow the reverse procedure as outlined above Recalibrate the instrument before putting it back into service Note The protective tape covering the J1 PWR and J2 GND terminals of new pow...

Страница 23: ...might adversely affect the performance of the instrument and could cause personal injury or property damage Replaceable Parts Note Contact your Emerson Process Management sales office for replacement power module FS numbers Standard Power Module Extended Life Power Module Note Neither Emerson Emerson Process Management nor any of their affiliated entities assumes responsibility for the selection u...

Страница 24: ... express or implied regarding the products or services described herein or their use or applicability All sales are governed by our terms and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice Neither Emerson Emerson Process Management nor any of their affiliated entities assumes responsibi...

Отзывы: