Product Certifications
83
Product Certifications
January 2017
Reference Manual
00809-0100-4853, Rev AB
Special Conditions for Safe Use (X):
1. If the equipment is fitted with the optional 90 V
transient suppressor, it is incapable of withstanding
the 500 V isolation from earth test and this must be
taken into account during installation.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however,
care should be taken to protect it from impact or
abrasion if located in a Zone 0 environment.
IG
IECEx FISCO
Certificate: IECEx BAS 08.0025X
Standards: IEC 60079-0:2011, IEC 60079-11:2011
Markings: Ex ia IIC T4 (–60 °C
≤
T
a
≤
+70 °C)
N7
IECEx Type n
Certificate: IECEx BAS 08.0026X
Standards: IEC
60079-0:2011,
IEC 60079-15:2010
Markings: Ex nA IIC T5 Gc (–40 °C
≤
T
a
≤
+70 °C)
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the
equipment is not capable of withstanding the 500 V
electrical strength test as defined in Clause 6.5.1 of IEC
60079-15:2010. This must be taken into account
during installation.
Brazil
E2
INMETRO Flameproof
Certificate: UL-BR 15.0393X
Standards: ABNT NBR IEC 60079-0:2008 +
Corrigendum 1:2011, ABNT NBR IEC
60079-1:2009 + Corrigendum 1:2011,
ABNT NBR IEC 60079-26:2008 +
Corrigendum 1: 2008
Markings: Ex d IICT* Ga/Gb, T6(–60 °C
≤
T
a
≤
+70 °C),
T5/T4(–60 °C
≤
T
a
≤
+80 °C), IP66
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the
environmental conditions to which the diaphragm will
be subjected. The manufacturer’s instructions for
installation and maintenance shall be followed in detail
to assure safety during its expected lifetime.
2. For information on the dimensions of the flameproof
joints, the manufacturer shall be contacted.
I2
INMETRO Intrinsic Safety
Certificate: UL-BR 15.0357X
Standards: ABNT NBR IEC 60079-0:2008 + Addendum
1:2011, ABNT NBR IEC 60079-11:2009
Markings: Ex ia IICT4 Ga, T4(–60 °C
≤
T
a
≤
+70 °C)
Special Conditions for Safe Use (X):
1. If the equipment is fitted with the optional 90 V
transient suppressor, it is incapable of withstanding
the 500 V isolation from earth test and this must be
taken into account during installation.
2. For processes with temperatures above 135 °C, the
user must assess whether the SuperModule
temperature class is suitable for such applications,
because in this situation there is a risk of the
SuperModule temperature being above T4.
Parameter
RTD (for 3051SFx)
(HART)
RTD for 3051SFx
(Fieldbus)
Voltage U
i
30 V
30 V
Current I
i
2.31 mA
18.24 mA
Power P
i
17.32 mW
137 mA
Capacitance C
i
0
0.8 nF
Inductance L
i
0
1.33 mH
Parameter
FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
0
Inductance L
i
0
Parameter
HART
Fieldbus
Input
RTD
Input
RTD
Voltage U
i
30 V
30 V
30 V
30 V
Current I
i
300 mA
2.31 mA
300 mA
18.24 mA
Power P
i
1 W
17.32 mW
1.3 W
137 mW
Capacitance C
i
14.8 nF
0
0
0.8 nF
Inductance L
i
0
0
0
1.33 mH
Содержание Rosemount MultiVariable 3051SMV
Страница 2: ......
Страница 6: ...vi Reference Manual 00809 0100 4853 Rev AB Contents January 2017 Contents ...
Страница 44: ...36 Reference Manual 00809 0100 4853 Rev AB Installation January 2017 Installation ...
Страница 62: ...54 Reference Manual 00809 0100 4853 Rev AB Troubleshooting January 2017 Troubleshooting ...
Страница 98: ...Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB Product Certifications 90 ...
Страница 99: ...Product Certifications 91 Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB ...
Страница 101: ...Product Certifications 93 Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB CO S CO O ...
Страница 106: ...Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB Product Certifications 98 CO S CO O ...
Страница 108: ...Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB Product Certifications 100 CO S CO O ...
Страница 111: ......