Product Certifications
January 2017
Reference Manual
00809-0100-4853, Rev AB
Product Certifications
82
International
E7
IECEx Flameproof and Dust
Certificate: IECEx KEM 08.0010X (Flameproof)
Standards: IEC 60079-0:2011, IEC 60079-1:2014, IEC
60079-26:2014
Markings: Ex db IIC T6…T4 Ga/Gb,
T6(–60 °C
≤
T
a
≤
+70 °C),
T5/T4(–60 °C
≤
T
a
≤
+80 °C)
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than
1 mm thickness that forms a boundary between EPL Ga
(process connection) and EPL Gb (all other parts of the
equipment). The model code and datasheet are to be
consulted for details of the diaphragm material.
Installation, maintenance and use shall take into
account the environmental conditions to which the
diaphragm will be subjected. The manufacturer's
instructions for installation and maintenance shall be
followed in detail to assure safety during its expected
lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from
electrostatic discharge. Avoid installations that could
cause electrostatic build-up on painted surfaces, and
only clean the painted surfaces with a damp cloth. If
paint is ordered through a special option code, contact
the manufacturer for more information.
4. Appropriate cable, glands and plugs need to be
suitable for a temperature of 5 °C greater than
maximum specified temperature for location where
installed.
Certificate: IECEx BAS 09.0014X (Dust)
Standards: IEC 60079-0:2011, IEC 60079-31:2008
Markings:
Ex ta IIIC T 105 °C T
500
95 °C Da,
(–20 °C
≤
T
a
≤
+85 °C), V
max
= 42.4 V
Special Conditions for Safe Use (X):
1. Cable entries must be used which maintain the ingress
protection of the enclosure to at least IP66.
2. Unused cable entries must be filled with suitable
blanking plugs which maintain the ingress protection
of the enclosure to at least IP66.
3. Cable entries and blanking plugs must be suitable for
the ambient temperature range of the apparatus and
capable of withstanding a 7J impact test.
4. The 3051S- SuperModule must be securely screwed in
place to maintain the ingress protection of the
enclosure.
I7
IECEx Intrinsic Safety
Certificate: IECEx BAS 08.0025X
Standards: IEC 60079-0:2011, IEC 60079-11:2011
Markings:
Ex ia IIC T4 Ga, T4(–60 °C
≤
T
a
≤
+70 °C)
Temperature class
Process temperature
T6
–60 °C to +70 °C
T5
–60 °C to +80 °C
T4
–60 °C to +120 °C
Parameter
HART
F
OUNDATION
Fieldbus
SuperModule
only
Voltage U
i
30 V
30 V
7.14 V
Current I
i
300 mA
300 mA
300 mA
Power P
i
1 W
1.3 W
887 mW
Capacitance C
i
14.8 nF
0
0.11 uF
Inductance L
i
0
0
0
Parameter
RTD (for 3051SFx)
(HART)
RTD for 3051SFx
(Fieldbus)
Voltage U
i
30 V
30 V
Current I
i
2.31 mA
18.24 mA
Power P
i
17.32 mW
137 mA
Capacitance C
i
0
0.8 nF
Inductance L
i
0
1.33 mH
Parameter
HART
®
F
OUNDATION
Fieldbus
SuperModule
only
Voltage U
i
30 V
30 V
7.14 V
Current I
i
300 mA
300 mA
300 mA
Power P
i
1 W
1.3 W
887 mW
Capacitance C
i
14.8 nF
0
0.11 uF
Inductance L
i
0
0
0
Содержание Rosemount MultiVariable 3051SMV
Страница 2: ......
Страница 6: ...vi Reference Manual 00809 0100 4853 Rev AB Contents January 2017 Contents ...
Страница 44: ...36 Reference Manual 00809 0100 4853 Rev AB Installation January 2017 Installation ...
Страница 62: ...54 Reference Manual 00809 0100 4853 Rev AB Troubleshooting January 2017 Troubleshooting ...
Страница 98: ...Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB Product Certifications 90 ...
Страница 99: ...Product Certifications 91 Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB ...
Страница 101: ...Product Certifications 93 Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB CO S CO O ...
Страница 106: ...Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB Product Certifications 98 CO S CO O ...
Страница 108: ...Product Certifications January 2017 Reference Manual 00809 0100 4853 Rev AB Product Certifications 100 CO S CO O ...
Страница 111: ......