Incorrect level when product surface is above 50%
Symptom
The reported level is incorrect when the product surface is above the 50% level.
Figure 7-10: Symptom
A
B
C
D
A. Level
B. Time
C. Actual level
D. Reported level
Possible cause
A strong double bounce echo is interpreted as the product surface.
Recommended actions
•
Enable the Double Bounce Handling function.
Related information
Handling strong double bounce echoes
Reference Manual
Service and troubleshooting
00809-0100-4418
September 2022
Rosemount 3408 Level Transmitter
79