Note
The surface echo is required to suppress the double bounce. If the surface echo enters the
Upper Null Zone, there is no product surface reference and the double bounce might be
interpreted as the surface echo.
The Double Bounce Handling function is only available in Rosemount Radar Master Plus.
Procedure
1. Read the echo curve plot to determine if double bounce echoes are present.
2. Select
Configure
→
Level Setup
→
Advanced
.
3. Under
More Advanced Options
, select
Echo Tracking
.
4. In the
Double Bounce Handling
list, select
Enabled
or
Disabled
.
5. If you enabled Double Bounce Handling, then enter desired Double Bounce Offset.
6. Select
Save
.
Related information
Double bounce offset
The distance between each double bounce echo is constant. The Double Bounce Offset is
used to define the distance between detected double bounces, as given by the following
formula (see
Double Bounce Offset = B - 2A
The Double Bounce Offset is negative if the reflection point (normally the tank roof) is
below the Tank Reference Point.
7.6
Service support
To expedite the return process, refer to
and contact the nearest Emerson
representative.
CAUTION
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of and understand the hazard. Returned products must include a copy of the
required Safety Data Sheet (SDS) for each substance.
Emerson representatives will explain the additional information and procedures necessary
to return goods exposed to hazardous substances.
Reference Manual
Service and troubleshooting
00809-0100-4418
September 2022
Rosemount 3408 Level Transmitter
103
Содержание Rosemount 3408
Страница 4: ...4 ...
Страница 14: ...Transmitter overview Reference Manual September 2022 00809 0100 4418 14 Emerson com Rosemount ...
Страница 28: ...Mechanical installation Reference Manual September 2022 00809 0100 4418 28 Emerson com Rosemount ...
Страница 38: ...Electrical installation Reference Manual September 2022 00809 0100 4418 38 Emerson com Rosemount ...
Страница 46: ...Configuration Reference Manual September 2022 00809 0100 4418 46 Emerson com Rosemount ...
Страница 54: ...Operation and maintenance Reference Manual September 2022 00809 0100 4418 54 Emerson com Rosemount ...
Страница 104: ...Service and troubleshooting Reference Manual September 2022 00809 0100 4418 104 Emerson com Rosemount ...