Reference Manual
00809-0100-4716, Rev JA
May 2008
Rosemount 3095 MultiVariable
3-16
HART
Changing the Atmospheric Pressure Value:
The Gauge Sensor on the 3095 takes measurements with respect to the
atmospheric pressure. To change the assumed atmospheric pressure value:
1.
Right-click on the transmitter icon.
2.
Highlight “Calibrate” from the pop-up menu.
3.
Highlight “Sensor Trim” from the submenu.
4.
Click on “Atmospheric Press.”
5.
A window appears, displaying the current atmospheric pressure value
used by the 3095. Select “Yes” to change the value, and click “Next”
(see Figure 3-13).
6.
Enter the new value for the atmospheric pressure, and click “Next.”
7.
Select the unit of measure from the drop-down menu, and click
“Next.”
8.
Select “Yes” to implement the new assumed Atmospheric Pressure
value, and click “Next.”
9.
Read the warning message, and click “Next.”
10. Click “Finish.”
Figure 3-13. Atmospheric
Pressure Configuration