The total resistance load is the sum of the resistance of the signal leads and the load resistance of the
controller, indicator, I.S. Barriers, and related pieces. If intrinsic safety barriers are used, the resistance
and voltage drop must be included.
4.6.3
Wiring the transmitter
Note
Use shielded twisted pairs to yield best results. To ensure proper communication, use 24 AWG or larger
wire and do not exceed 5000 ft. (1500 m).
Figure 4-6. 4–20 mA HART
A. DC power supply
B. R
L
≥
250 (necessary for HART communication only)
Perform the following procedure to make wiring connections:
1. Remove the housing cover on terminal compartment side. Do not remove the cover in explosive
atmospheres when the circuit is live. Signal wiring supplies all power to the transmitter.
Maximum loop resistance = 43.5
⫻
(Power supply voltage – 10.5)
The Field Communicator requires a minimum loop resistance of 250
Ω
for communication.
Do not connect the power signal wiring to the test terminals. Incorrect wiring can damage test circuit.
V
Lo
ad
(
Ω
s)
Operating
Region
1387
1000
500
0
10.5
20
30
42.4
A
B
Содержание Rosemount 2051G
Страница 2: ......
Страница 10: ...2 Reference Manual 00809 0400 4101 Rev BA Introduction January 2018 Introduction ...
Страница 34: ...26 Reference Manual 00809 0300 4410 Rev BA Configuration January 2018 Configuration ...
Страница 64: ...56 Reference Manual 00809 0400 4101 Rev BA Operation and Maintenance January 2018 Operation and Maintenance ...
Страница 72: ...64 Reference Manual 00809 0400 4101 Rev BA Troubleshooting January 2018 Troubleshooting ...
Страница 89: ......